Generac Power Systems 9 kW NG ユーザーズマニュアル

ページ / 192
TRANSFER SWITCH
sEctioN 3.1
DEscriPtioN & comPoNENts
Part 3
Page 57
tranSFer mechaniSm
The  2-pole  transfer  mechanism  consists  of  a  pair 
of  moveable  LOAD  contacts,  a  pair  of  stationary 
UTILITY contacts, and a pair of stationary STANDBY 
contacts.  The  load  contacts  can  be  connected  to 
the  utility  contacts  by  a  utility  closing  coil;  or  to  the 
standby  contacts  by  a  standby  closing  coil.  In  addi-
tion,  the  load  contacts  can  be  actuated  to  either  the 
UTILITY  or  STANDBY  side  by  means  of  a  manual 
transfer handle. See Figures 2 and 3. 
STANDBY
LOAD
UTILITY
Figure 2. Load Connected to Utility Power Source 
STANDBY
LOAD
UTILITY
Figure 3. Load Connected to Standby Power Source 
UTILITY CLOSING COIL C1:
See  Figure  4. This  coil  is  energized  by  rectified  util-
ity  source  power,  to  actuate  the  load  contacts  to  the 
UTILITY power source side. When energized, the coil 
will  move  the  main  contacts  to  an  “overcenter”  posi-
tion.  A  limit  switch  will  then  be  actuated  to  open  the 
circuit and spring force will complete the retransfer to 
STANDBY. A bridge rectifier, which changes the utility 
source alternating current (AC) to direct current (DC), 
is sealed in the coil wrappings. If coil or bridge rectifier 
replacement  becomes  necessary,  the  entire  coil  and 
bridge assembly should be replaced. 
STANDBY CLOSING COIL C2:
Coil  C2  is  energized  by  rectified  standby  source 
power, to actuate the load contacts to their “Standby” 
source  side.  Energizing  the  coil  moves  the  load  con-
tacts to an overcenter position; limit switch action then 
opens  the  circuit  and  spring  force  will  complete  the 
transfer action to “Standby”. This coil’s bridge rectifier 
is  also  sealed  in  the  coil  wrappings.  Replace  the  coil 
and bridge rectifier as a unit. 
LIMIT SWITCHES SW2 AND SW3:
Switches are mechanically actuated by load contacts 
movement. When the load contacts are connected to 
the utility contacts, limit switch SW2 opens the utility 
circuit  to  utility  closing  coil  C1  and  limit  switch  SW3 
closes the standby circuit to standby closing coil C2. 
The  limit  switches  “arm”  the  system  for  retransfer 
back  to  UTILITY  when  the  load  contacts  are  con-
nected  to  the  STANDBY  side.  Conversely,  when  the 
load contacts are connected to the UTILITY side, the 
switches  “arm”  the  system  for  transfer  to  STANDBY. 
An  open  condition  in  limit  switch  SW2  will  prevent 
retransfer to “Utility”. An open switch SW3 will prevent 
transfer to STANDBY.
UTILITY
CLOSING
COIL (C1)
STANDBY
CLOSING
COIL (C2)
BRIDGE
RECTIFIER
BRIDGE
RECTIFIER
MANUAL
TRANSFER
LEVER
LIMIT 
SWITCH 
(SW2)
N1
N2
E2
E1
T1
LIMIT 
SWITCH 
(SW3)
T2
N2A
A
A
B
126
205
B
E2
Figure 4. The “W/V-Type” Transfer Mechanism 
tranSFer relay
Transfer  relay  operation  is  controlled  by  a  circuit 
board. That  circuit  board  is  a  part  of  a  control  panel 
assembly, mounted on the standby generator set. 
Figure  5  shows  the  transfer  relay  pictorially  and 
schematically.  Relay  operation  may  be  briefly 
described as follows: 
1.  Generator  battery  voltage  (12  volts  DC)  is  available  to 
the transfer relay coil from the generator circuit board, 
via Wire 15B and Relay Terminal A.
a.  The  12  volts  DC  circuit  is  completed  through 
the transfer relay coil and back to the generator 
circuit board, via Wire 23. 
b.  Circuit board action normally holds the Wire 
23  circuit  open  to  ground  and  the  relay  is 
de-energized.