9300 Series User’s Guide
Using the Optional Analog Outputs
Chapter 5 - Features and Applications 
Page 125
The settings for Analog Input modules are as follows: 
1
An arbitrary input value can be treated as the Zero Scale (i.e. a 4-20mA input is capable of generating 
a 0 to X output).
Using the Optional Analog Outputs
The four optional Analog Output ports can output energy pulses to an RTU or 
perform equipment control operations. Both types of Analog Output (either 0-
20mA or 0-1mA) can deliver a continuous DC signal. Analog Output modules 
control these hardware ports.
You use ION Designer to create and configure these ION modules. Create an 
Analog Output module for each output port you are going to use, and link their 
Source input to a value you want to reflect through the analog outputs. Alter the 
setup registers as required:
 
Setting Zero Scale for 4 to 20mA Outputs
If you want your 9300 meter’s 0 to 20 mA analog output ports to operate as 4 to 20 
mA outputs (i.e. delivers a 4 mA current with a zero Source input value to the 
Analog Output module), use the following formula:
Zero Scale = - 0.25 * Full Scale
For example, with a Full Scale value of 100, your Zero Scale setting would be -25.
Setup 
Registers
Available Settings
Creation 
Default
Description
Port
Not Used
I/O Exp AI1 to 
I/O Exp AI4
Not Used
The input hardware channel
Full Scale
-1 x 10
9
 to 1 x 10
9
1
Defines what value appears in the ScaledValu 
output register when the highest possible value 
from the hardware is applied
Zero Scale 
1
-1 x 10
9
 to 1 x 10
9
0
Defines what value appears in the ScaledValu 
output register when the lowest possible value 
from the hardware is applied
Setup 
Registers
Available Settings
Creation 
Default
Description
Port
Not Used
I/O AO1 to
I/O AO4 inclusive
Not Used
The output hardware channel
Full Scale
-1 x 10
9
 to 1 x 10
9
1
Defines what value appears in the ScaledValu 
output register when the highest possible value 
from the hardware is applied
Zero Scale
-1 x 10
9
 to 1 x 10
9
0
Defines what value appears in the ScaledValu 
output register when the lowest possible value 
from the hardware is applied