Clear Functions Menu
 9300 Series User’s Guide
Page 28
Chapter 2 - Using The Front Panel 
Editing Registers
To edit the value of a register, navigate the registers using the arrow keys until the 
register you want is highlighted, then press the round button. The register appears 
in one of two ways: as a number, or as an option selected from a menu. Once you 
have entered the password (if required), a Y
ES
 or N
O
 verification screen appears 
showing the new value of the register. Select Y
ES
 to change the value of the setup 
register; select N
O
 to return to the previous screen without changing the value.
Numeric Registers
Use the arrow buttons to change the value of the digit above the 
 cursor. 
Change the position of the cursor by holding down an arrow key for about one 
second. Holding the up arrow button moves the cursor left one position, and 
holding the right arrow button moves the cursor right one position. Once you have 
the value you want, press the round button.
Enumerated Registers
Some registers are displayed as a menu of options. The current value of the register 
will be displayed in the list with an asterix (*) on either side of it. Use the arrow 
buttons to highlight the setting you want, and press the round button. 
Front Panel Password Security
The password is required when you make a change to a register through the front 
panel. Once you have entered a valid password, you can make multiple register 
changes. The password is factory set at ‘00000’ (5 zeros). Press the round button 
when you have entered the correct front panel password. If you need to change the 
password, refer to the section “Security Menu” on page 35.
Clear Functions Menu
The C
LEAR
 F
UNCTIONS
 menu allows you to reset cumulative parameters. To access 
the Clear Functions screen, press the round button while the meter is displaying 
data; scroll down the Setup menu and select C
LEAR
 F
UNCTIONS
.
Peak Demand Reset
The following Demand parameters are reset when you select P
EAK
 D
MD
 R
SET
:
Maximum and Minimum Rolling (Sliding Window) Demand (kW, kVAR, kVA)
Maximum and Minimum Thermal Demand (kW, kVAR, kVA)
Min/Max Reset
The minimum and the maximum values for each the following parameters are reset 
when you select M
N
M
X
 R
SET
:
Phase and average Current
Line-to-line voltages
Line-to-neutral voltages
Frequency
PF lead and PF lag
Total kW, kVAR, kVA