Communications Setup
Chapter 3 - Default Meter Functionality 
Page 43
Communications Setup
Communication settings are typically configured when the ACCESS meter is 
initially put into service. Each communications port on a meter is controlled by a 
single Communications module. The modules’ setup registers define the 
parameters used for each port, so parameters do vary according to the type of 
communications channel selected (i.e. RS-232, RS-485, Modem, Infrared, Ethernet).
1
For 9330 / 9350 meters with an optional modem, COM1 is hardwired for ModemGate.
2
COM2
 is 
not available for the 9300 meter. 
3
For 9330 / 9350 meters with an optional Ethernet card, COM2 is hardwired for EtherGate.
4 Available for the 9300 meter.
A communications channel must be configured before you can use ACCESS 
software (i.e. Vista or Designer). Altering the settings of the channel that is in use 
causes a loss of communications with the meter. Refer to the online ION 
Programmer’s Referenc
e for complete details on all the Communications module 
setup registers. 
1
The factory set Unit ID for this port is based on the serial number of the meter. For example: Serial 
number: PA-0009A263-10; Unit ID: 9263.
2
Setting for the 9330 and 9350 meters.
Module Name
Settings
Comm 1
COM1 RS-485 port and internal modem 
1
Comm 2 
2
COM2 RS-485 port or EtherGate 
3
 port
Infrared Comm
COM3 Optical port
Ethernet Comm
10Base-T Ethernet port
Profibus Comm 
4
Profibus Communications port
Communications 
Module
Setup Register
Description
Default
Comm 1
Comm 2
Infrared Comm
Baud Rate
Sets the communications speed, in bits/second for the serial port
9600
RTS Delay
Sets the RTS Delay for the serial communications port
0
Unit ID
Sets the Unit ID of the communications port
Unit ID is based on 
the serial number 
1
Protocol
Sets the communications protocol for the communications port
ION
Comm 1
Modem Init 
2
Sets the modem’s initialization string
AT&F
Ethernet
IP Address
Sets the IP Address of the meter
None
Subnet Mask
Sets the Subnet Mask setting for the Ethernet Port
None
Gateway
Sets the Ethernet Gateway setting for the Ethernet Port
None
SMTP Server 
3
Sets the IP Address for the SMTP Mail Server that is configured to 
forward mail from the meter to the final destination 
None
SMTP Connection
Timeout 
3
Sets the time that the meter will wait when establishing a 
connection to an SMTP Server
None
Profibus Comm
PB Address
Sets the Profibus Address
126