Electrical safety
Perform the electric safety check after completing installation:
Gas leak check
Soap water method
Apply a soap water or a liquid neutral 
detergent on the indoor unit 
connection or outdoor unit connections 
by a soft brush to check for leakage of 
the connecting points of the piping. If 
bubbles come out, the pipes have 
Leak detector
Use the leak detector to check for 
leakage.
Caution
A: Lo packed valve, B: Hi packed valve 
C and D are ends of indoor unit 
connection.
Outdoor unit
check point
Cover
indoor unit
check point
1. Insulated resistance: The insulated resistance must be more than 2M    .
2. Grounding work: After finishing grounding work, measure the grounding 
resistance by visual detection and grounding resistance tester. Make sure the 
grounding resistance is less than 4    .
3. Electrical leakage check (performing during test running): During test operation 
after finishing installation, the serviceman can use the electric probe and 
multimeter to perform the electrical leakage check. Turn off the unit 
immediately if electrical leakage happens. Check and find out the solution
ways till the unit operates properly.
Electrical safety and gas leak check
leakage point.