“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
P
a
ra
meters
3–56
Analog Summary Table - The following table shows all eight functions available for assign-
ment to the three analog output terminals [FM], [AM], [AMI] at a glance. Detailed descrip-
tions, related parameters and settings, and example wiring diagrams are in 
23
POK
Positioning completion
ON
when the load position is at the target
OFF
when the load position is not yet at the target
24
FA4
Frequency arrival type 
4 – over-frequency (2)
ON
when output to motor is at or above the FA threshold 
2 (C045) during accel
OFF
when the output to motor is below the FA threshold 2 
(C046) during decel
25
FA5
Frequency arrival type 
5 – at frequency (2)
ON
when output to motor is at the FA threshold 2 (C045) 
during accel, or at C046 during decel
OFF
when the output to motor is not at either the FA 
threshold 2 (C045) during accel or at C046 during 
decel
26
OL2
Overload notice 
advance signal (2)
ON
when output current is more than the set threshold for 
the overload signal
OFF
when output current is less than the set threshold for 
the overload signal
Output Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description
Analog Output Function Summary Table
Option
Code
Function Name
Description
Corresponding Signal 
Range
00
Output frequency
Actual motor speed, represented by PWM 
signal 
0 to max. frequency in Hz
01
Output current
Motor current (% of maximum rated output 
current), represented by PWM signal
0 to 200%
02
Output torque
Rated output torque
0 to 200%
03
Digital output 
frequency
Output frequency (available only at FM 
output)
0 to max. frequency in Hz
04
Output voltage
Rated output voltage to motor
0 to 100%
05
Input power
Rated input power
0 to 200%
06
Electronic thermal 
overload
Percentage of electronic overload attained
0 to 100%
07
LAD frequency
Internal ramp generator frequency
0 to max. frequency in Hz