Mitsubishi Electronics A800 ユーザーズマニュアル

ページ / 116
106
Appendix1
For customers replacing the 
conventional model with this 
inverter
Appendix1.1
Replacement of the FR-A740 series
Difference and compatibility with FR-A740 series
Installation precautions
 • Removal procedure of the front cover is different. (Refer to 
.)
 • Plug-in options of the FR-A700 series are not compatible.
 • Operation panel (FR-DU07) cannot be used.
Item
FR-A740
FR-A842
Control method
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (with plug-in option used)
PM sensorless vector control (IPM motor)
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (with plug-in option used)
PM sensorless vector control (IPM motor/SPM motor)
Added functions
-
USB host function
Safety stop function
etc.
M
a
xi
mum
 outp
u
t freq
uenc
y
V/F control
400 Hz
590 Hz
Advanced 
magnetic flux 
vector control
120 Hz
400 Hz
Real sensorless 
vector control
120 Hz
400 Hz
Vector control
120 Hz
400 Hz
PM sensorless 
vector control 
(MM-CF)
300 Hz
400 Hz
PID control
Turn the X14 signal ON to enable PID control.
The X14 signal does not need to be assigned. (PID control 
is available by the Pr.128 setting.) 
The PID pre-charge function and dancer control are 
added.
Automatic restart after 
instantaneous power 
failure
Turn the CS signal ON to restart.
CS signal assignment not required. (Restart is enabled 
with the Pr.57 setting only.)
Number of motor poles
V/F control switching
The V/F switchover (X18) signal is valid when 
Pr.81 = "12 to 20 (2 to 10 poles)".
Pr.81= "12 (12 poles)"
X18 is valid regardless of the Pr.81 setting. (The Pr.81 
settings "14 to 20" are not available.)
PTC thermistor input
Input from the terminal AU
(The function of the terminal AU is switched by a 
switch.)
Input from the terminal 2.
(The function of the terminal 2 is switched by the Pr.561 
setting.)
USB connector
B connector
Mini B connector
Control circuit terminal block Removable terminal block (screw type)
Removable terminal block (spring clamp type)
Terminal response level
The FR-A800's I/O terminals have better response level than the FR-A700's terminals. By setting Pr.289 
Inverter output terminal filter
 and Pr.699 Input terminal filter, the terminal response level can be 
compatible with that of FR-A700. Set to approximately 5 to 8 ms and adjust the setting according to the 
system.
PU
FR-DU07 (4-digit LED)
FR-PU07
FR-DU08 (5-digit LED)
FR-PU07 (Some functions, such as parameter copy, are 
unavailable.)
FR-DU07 is not supported.
Plug-in option
Dedicated plug-in options (not interchangeable)
Communication option
Connected to the connector 3.
Connected to the connector 1.
Installation size
Installation size is not compatible. (New mounting holes are required.)
Converter
Built in for all capacities
The converter unit (FR-CC2) is required.
DC reactor
DC reactor (FR-HEL) is provided.
Built in the converter unit (FR-CC2)