Mitsubishi Electronics A800 ユーザーズマニュアル

ページ / 116
Main circuit terminals
28
2.5
Main circuit terminals
2.5.1
Details on the main circuit terminals of the 
inverter
2.5.2
Details on the main circuit terminals of the 
converter unit (FR-CC2)
Terminal 
symbol
Terminal name
Terminal function description
Refer 
to page
U, V, W
Inverter output
Connect these terminals to a three-phase squirrel cage motor or an PM 
motor.
-
R1/L11,
S1/L21
Power supply for the control 
circuit
Connected to the terminals P/+ and N/-. To retain the fault display and fault 
output, or to use the converter unit (FR-CC2), remove the jumpers installed in 
terminals R1/L11 and S1/L21, and apply external power supply to these 
terminals.
The power capacity necessary when separate power is supplied from R1/L11 
and S1/L21 is 80 VA.
P/+, N/-
Converter unit connection
Connect the converter unit (FR-CC2), brake unit (FR-BU2), or high power 
factor converter (FR-HC2).
Earth (ground)
For earthing (grounding) the inverter chassis. This must be earthed 
(grounded).
Terminal 
symbol
Terminal name
Terminal function description
Refer 
to page
R/L1,
S/L2,
T/L3
AC power input
Connect these terminals to the commercial power supply.
-
R1/L11,
S1/L21
Power supply for the control 
circuit
Connected to the AC power supply terminals R/L1 and S/L2. To retain the 
fault display and fault output, remove the jumpers across terminals R/L1 and 
R1/L11 and across S/L2 and S1/L21, and supply external power to these 
terminals.
The power capacity necessary when separate power is supplied from R1/L11 
and S1/L21 is 80 VA.
P/+, N/-
Inverter connection
Connect to terminals P/+ and N/- of the inverter.
Earth (ground)
For earthing (grounding) the converter unit chassis. This must be earthed 
(grounded).