Caution
Transportation and Mounting
The storage temperature (applicable for a short time, e.g. during 
transit) must be between -20 and +65°C. Otherwise the inverter 
may be damaged.
The inverter must be used indoors (without corrosive gas, 
flammable gas, oil mist, dust and dirt etc.) Otherwise the inverter 
may be damaged.
The inverter must be used at an altitude of 2500 m or less above 
sea level, with 2.9 m/s
2
 or less vibration at 10 to 55 Hz 
(directions of X, Y, Z axes).  Otherwise the inverter may be 
damaged. (Refer to 
 for details.)
If halogen-based materials (fluorine, chlorine, bromine, iodine, 
etc.) infiltrate into a Mitsubishi product, the product will be 
damaged. Halogen-based materials are often included in 
fumigant, which is used to sterilize or disinfest wooden 
packages. When packaging, prevent residual fumigant 
components from being infiltrated into Mitsubishi products, or 
use an alternative sterilization or disinfection method (heat 
disinfection, etc.) for packaging. Sterilization of disinfection of 
wooden package should also be performed before packaging 
the product.
Wiring
Do not install a power factor correction capacitor or surge 
suppressor/capacitor type filter on the inverter output side. 
These devices on the inverter output side may be overheated or 
burn out.
The output side terminals (terminals U, V, and W) must be 
connected correctly. Otherwise the motor will rotate inversely.
PM motor terminals (U, V, W) hold high-voltage while the PM 
motor is running even after the power is turned OFF. Before 
wiring, the PM motor must be confirmed to be stopped. 
Otherwise you may get an electric shock.
Never connect an PM motor to the commercial power supply.
Applying the commercial power supply to input terminals (U,V, 
W) of an PM motor will burn the PM motor.  The PM motor must 
be connected with the output terminals (U, V, W) of the inverter.
Trial run
Before starting operation, each parameter must be confirmed 
and adjusted. A failure to do so may cause some machines to 
make unexpected motions.
Warning
Usage
Everyone must stay away from the equipment when the retry 
function is set as it will restart suddenly after a trip.
Since pressing a key may not stop output depending on 
the function setting status, separate circuit and switch that make 
an emergency stop (power OFF, mechanical brake operation for 
emergency stop, etc.) must be provided.
OFF status of the start signal must be confirmed before resetting 
the inverter fault. Resetting inverter fault with the start signal ON 
restarts the motor suddenly.
Do not use an PM motor for an application where the PM motor 
is driven by its load and runs at a speed higher than  the 
maximum motor speed.
Use this inverter only with three-phase induction motors or with 
an PM motor. Connection of any other electrical equipment to 
the inverter output may damage the equipment.
Performing pre-excitation (LX signal and X13 signal) under 
torque control (Real sensorless vector control) may start the 
motor running at a low speed even when the start command 
(STF or STR) is not input The motor may run also at a low speed 
when the speed limit value = 0 with a start command input. It 
must be confirmed that the motor running will not cause any 
safety problem before performing pre-excitation.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this 
manual. Doing so may lead to fault or damage of the product.
Caution
Usage
The electronic thermal relay function does not guarantee 
protection of the motor from overheating. It is recommended to 
install both an external thermal and PTC thermistor for overheat 
protection.
Do not use a magnetic contactor on the inverter input for 
frequent starting/stopping of the inverter. Otherwise the life of the 
inverter decreases.
The effect of electromagnetic interference must be reduced by 
using a noise filter or by other means. Otherwise nearby 
electronic equipment may be affected.
Appropriate measures must be taken to suppress harmonics. 
Otherwise power supply harmonics from the inverter may heat/
damage the power factor correction capacitor and generator.
When driving a 400V class motor by the inverter, the motor must 
be an insulation-enhanced motor or measures must be taken to 
suppress surge voltage. Surge voltage attributable to the wiring 
constants may occur at the motor terminals, deteriorating the 
insulation of the motor.
When parameter clear or all parameter clear is performed, the 
required parameters must be set again before starting 
operations. because all parameters return to their initial values.
The inverter can be easily set for high-speed operation. Before 
changing its setting, the performances of the motor and machine 
must be fully examined.
Stop status cannot be hold by the inverter's brake function. In 
addition to the inverter’s brake function, a holding device must 
be installed to ensure safety.
Before running an inverter which had been stored for a long 
period, inspection and test operation must be performed.
Static electricity in your body must be discharged beforeyou 
touch the product.
Only one PM motor can be connected to an inverter.
An PM motor must be used under PM sensorless vector control. 
Do not use a synchronous motor, induction motor, or 
synchronous induction motor. 
Do not connect an PM motor in the induction motor control 
settings (initial settings). Do not use an induction motor in the 
PM sensorless vector control settings.  It will cause a failure.
In the system with an PM motor, the inverter power must be 
turned ON before closing the contacts of the contactor at the 
output side.
Emergency stop
A safety backup such as an emergency brake must be provided 
to prevent hazardous conditions to the machine and equipment 
in case of inverter failure.
When the breaker on the inverter input side trips, thewiring must 
be checked for fault (short circuit), and internalparts of the drive 
unit for a damage, etc. The cause of the trip must be identified 
and removed before turning ON the power of the breaker.
When a protective function activates, take an appropriate 
corrective action, then reset the inverter, and resume the 
operation.
Maintenance, inspection and parts replacement
Do not carry out a megger (insulation resistance) test on the 
control circuit of the inverter. It will cause a failure.
Disposal
The inverter must be treated as industrial waste.
General instruction
Many of the diagrams and drawings in the Instruction Manual 
show the product without a cover or partially open for 
explanation. Never operate the product in this manner. The 
cover must be always reinstalled and the instruction in the 
Instruction Manual must be followed when operating the product. 
For more details on the PM motor, refer to the Instruction Manual 
of the PM motor.