Electro-magnetic interference (EMI) and leakage currents
61
3
Selecting the rated sensitivity current for the earth leakage circuit 
breaker
When using an earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows, 
independently of the PWM carrier frequency.
 • Inverter/converter unit leakage current
400 V class (input power condition: 440 V/60 Hz, power supply unbalance within 3%)
 • Breaker designed for harmonic and surge suppression
Rated sensitivity current
I
n  10  (Ig1 + Ign + Igi + Ig2 + Igm)
 • Standard breaker
Rated sensitivity current
I
n  10  {Ig1 + Ign + Igi + 3  (Ig2 + Igm)}
Ig1, Ig2:  Leakage currents in wire path during commercial 
power supply operation
Ign: 
Leakage current of inverter input side noise filter
Igm: 
Leakage current of motor during commercial power 
supply operation
Igi: 
Leakage current of inverter unit
(When the converter unit is connected, add the 
leakage current of converter unit.)
<Example>
 • Selection example for the   connection of the 400 V class
Item
Breaker designed 
for harmonic and 
surge suppression
Standard breaker
Leakage current Ig1 (mA)
1
66 
5 m
= 0.11
3
1000 m
Leakage current Ign (mA)
0 (without noise filter)
Leakage current Igi (mA)
1 (without EMC filter)
For the leakage current of the inverter, refer to 
the following table.
Leakage current Ig2 (mA)
1
66 
60 m
= 1.32
3
1000 m
Motor leakage current Igm (mA)
0.36
Total leakage current (mA)
2.79
6.15
Rated sensitivity current (mA) (
 Ig  10) 30
100
Inverter/
converter unit
FR-A800
(Standard model)
FR-A802
(Separated converter type)
Converter unit FR-CC2
H315K, H355K
H400K to H500K
EMC filter
ON
OFF
-
ON
OFF
ON
OFF
35
2
2
35
2
70
2
2
1
1
2
1
2
1
(mA)
Motor capacity (kW)
For "   " connection, the amount of leakage current is appox.1/3 of the above value.
(Three-phase three-wire delta
 connection 400V60Hz)
Example of leakage current per 1km during 
the commercial power supply operation 
when the CV cable is routed in metal conduit
Leakage current example of three-
phase induction motor during the 
commercial power supply operation
(Totally-enclosed fan-cooled
 type motor 400V60Hz)
0
2 0
4 0
6 0
8 0
100
120
leakage currents (mA)
leakage currents (mA)
2 3.5
5.5
8 1422
30
38
60
80
100
150
Cable size (mm
2
)
0. 1
0. 2
0. 3
0. 5
0. 7
1. 0
2. 0
1. 5 3. 7
2. 2
7. 5 1522
11
37
30
55
45
5.5
18. 5
Noise 
filter
Inverter
ELB
Ig1
Ign
Igi
Ig2
Igm
M
5.5mm
   5m
5.5mm
2    
60m
400V
2.2kW
3
φ
Phase 
earthing
(grounding)
Earthed-neutral 
system