38
Freedom SW 230V Installation Guide
Installing the Inverter/Charger
Step 7: Performing Checks Prior to Initial Start-Up
Before testing your installation, ensure these conditions are met:
❐
Chassis and AC grounds are properly installed
❐
AC input connections and AC output connections are wired
correctly on the terminal block and not reversed
correctly on the terminal block and not reversed
❐
Positive (+) battery cable is connected to the positive (+)
battery terminal through the DC fuse and disconnect switch or
DC circuit breaker
battery terminal through the DC fuse and disconnect switch or
DC circuit breaker
❐
Negative (–) battery cable is connected to the negative (–)
battery terminal
battery terminal
❐
Battery voltage is within the proper range of 20–32 volts DC
❐
DC disconnect switch or breaker is turned off
❐
AC input and output breakers are turned off
❐
All connections are tight
Freedom SW 3K2K 230V InvChg Install Guide.book Page 38 Friday, June 20, 2014 9:11 AM