6 – 2
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
As mentioned in the above paragraph, the distance of 
the process variable from the control setpoint deter-
mines the size of the pulse used to move the capacity 
slide. This is called the proportional band and is set by 
the Proportional Setpoint. When the process variable is 
outside the proportional band, the slide will move in the 
direction of the error continuously. Increasing the size 
of the proportional band can help slow the compres-
sors reaction by varying loads if desired, see Figure 6-2. 
Proportional Band & Setpoint.
The Dead Band Setpoint defi nes area around the control 
setpoint where the algorithm stops adjusting the capac-
ity slide. This area is a percentage of the proportional 
band. By default the proportional band is set to 4 Psig 
and the dead band is set to 10% of 4 Psig. Making the 
dead band +/- 0.4 Psig of the control setpoint. Once the 
process variable is within the dead band, the algorithm 
considers the compressor to be on setpoint. If the op-
erator wishes the compressor to operate closer, the set-
point can be set to a smaller percentage. However this 
will result in the capacity slide excessively moving to 
maintain the setpoint and could over heat the actuator 
or shorten the actuators operational life.
Auto-Cycle
The auto-cycle setpoints defi ne the control points in 
which the compressor will automatically cycle on and off 
when the compressor has been placed into “Auto” run 
mode. These setpoints can be “enabled” or “disabled” 
using the check box. A delay can be entered to momen-
tarily delay the start or stop from immediately occurring 
when the setpoint is met. If a compressor shutdown is 
desired on a suction pressure drop and a manual reset 
is required, set the OFF value below the Low Suction 
Pressure safety trip value. This will shut down the com-
pressor and a Reset will be required to restart it.
Section 6 • Compressor Control
Figure 6-2. Proportional Band & Setpoint