Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Analog Inputs
This section of the Calibration screen allows the opera-
tor to defi ne the parameters of an installed auxiliary ana-
log instrument. These instruments are usually not part 
of a typical compressor setup but Vission 20/20 provides 
a way for the operator to add additional capabilities. The 
layout of this screen is typical to the pressure and tem-
perature calibration screens.
Device Calibration:
•  These setpoints allow the operator to defi ne what the 
input from the auxiliary instrument means in terms 
of units and range. If a temperature measuring in-
strument is connected, then the operator would se-
lect temperature from the Unit drop-down box then 
set the maximum and minimum value for the scale.
Offset:
•  Once the two-point calibration is completed, it is not 
uncommon for there to be a small error. By entering 
the value of the error from the calibrated value and 
the actual value into the adjustment entry box, that 
error will be added/subtracted from the total offset. 
The offset is applied to the calibrated value which 
should correct the error.
Range:
•  Here the operator defi nes the signal type and range 
transmitted by the instrument. The operator can 
choose from several predefi ned ranges in the drop-
down box or enter a value.
Section 13 • Instruments Calibration