Emerson 20/20 ユーザーズマニュアル

ページ / 120
14 – 3
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
4. From the main screen select the Menu button.
5. On the menu screen select the Slide Calibration but-
ton. When the “Slide Valve Calibration” screen appears, 
then you can safely connect the Power Cable (Yellow 
TURCK cable) and the Position Transmitter Cable (Gray 
TURCK cable) to the Capacity motor. Press “+” or “-” to 
move the slide valves to check the rotation. (See Table 1 
below for proper shaft rotation). If for any reason the “+” 
or “-” command on the panel does not correspond to the 
slide increase or decrease, swap the blue & brown wires 
of the Yellow TURCK cable in the control panel to reverse 
the rotation of the motor.
CAUTION
DO NOT CONTINUE TO ENERGIZE THE ACTUATOR
MOTOR AFTER THE SLIDE HAS REACHED THE
MECHANICAL STOP. Doing so may cause mechanical
damage to the motor or shear the motor shaft
key. When the slide has reached the mechanical
stop position, press the button in the center of the
photochopper to release the brake, and thereby
release the tension on the actuator motor.
6. Quickly press and release the BLUE CALIBRATION 
BUTTON on the ACTUATOR motor once. This instructs 
the ACTUATOR motor to enter the calibration mode. The 
red LED on the actuator control board will begin fl ash-
ing. Use the “-” button on the Vission 20/20 panel to 
drive the capacity slide to its minimum mechanical stop 
position.
This will be apparent by a slowing of the motor rotation 
and a winding sound from the actuator motor. When 
you hear the motor wind-up, release the “-” button.
Then use the “+” button to pulse the motor so that the 
capacity slide is “just off” of its minimum position and 
there is no tension on the motor shaft.
7. Quickly press and release the BLUE CALIBRATION 
BUTTON on the ACTUATOR motor once. The red LED 
will now fl ash at a slower rate. This now instructs the 
ACTUATOR motor that this point is the minimum slide 
position. This point will correspond to 0 volts AFTER the 
ACTUATOR calibration procedure is completed.
8. Use the “+” button on the Vission 20/20 to drive the 
capacity slide to its maximum mechanical stop position. 
This will be apparent by a slowing of the motor rotation 
and a winding sound from the actuator motor. When 
you hear the motor wind-up, release the “+” button.
9. Quickly press and release the BLUE CALIBRATION 
BUTTON on the ACTUATOR motor once. The RED LED 
will stop fl ashing. This now instructs the ACTUATOR mo-
tor that this point is the maximum slide position. This 
point corresponds to 5 volts. The ACTUATOR calibration 
procedure is completed.
Now the Capacity Channel is automatically calibrated 
based on the calibration settings made to the actuator.
Figure 14-2. Photochopper
CAUTION
Do not over tigten screws. Failure to comply may 
result in damage to equipment.
10. Gently lower the plastic cover to where it contacts 
the base and O-ring seal. After making sure that the 
cover is not binding, gently tighten the four # 10 Phillips 
screws.
11. Repeat the same procedure for the Volume slide 
motor.
Section 14 • Slide Calibration