All electrical service work on 
your JET sander should be performed by a 
qualified, licensed electrician who is familiar with 
all safe standard electrical installation practices 
and all applicable electrical codes. This includes 
local electrical codes which may affect the 
connection and operation of the sander in your 
specific manufacturing operation.
 
9.1  Single phase electrical hookup 
When connecting your machine to single phase 
power, you may be connecting to either 115 or 230 
volts, depending upon the motor type provided. Local 
codes may, or may not, permit the use of a plug type 
of connection for your machine. Where a plug 
connection is permitted, the following installation 
practices must be followed: 
1.  The plug used must be a grounding type of plug. 
That is, on a 115 volt single phase connection, 
the plug must be a three-prong plug with two flat, 
parallel blades for the power wires and a single 
rounded or U-shaped prong for the ground 
connection. On 230 volt single phase 
connections, the lug must be a three prong plug 
with two flat blades in tandem to carry the 
current, and a third round or U-shaped prong for 
the ground connection. 
2.  The service branch to which the plug is 
connected must be a branch with a separate 
ground wire so the grounding prong of the plug 
can be connected to ground effectively. 
Note: Local electrical codes in many jurisdictions 
DO NOT ALLOW THE USE OF PLUG TYPE 
CONNECTIONS FOR SINGLE PHASE POWER 
WHEN THE MACHINE IS USED IN A COMMERCIAL 
OR INDUSTRIAL ESTABLISHMENT. 
 
 In these cases you must connect your machine to the 
service branch using a hardwired junction box 
connection. 
Motor rotation 
The motor's rotation should result in the belt sander 
moving downward and the disc sander rotating 
counterclockwise. 
Voltage conversion 
Single phase machines are pre-wired for 115V or 
230V per customer request. If it becomes necessary 
to change the voltage, remove the back cover from 
the base and place the machine on its side. Remove 
the terminal cover from the motor. Rewire the motor 
according to the motor connection diagram in section 
12.1. Different electrical plugs are required depending 
on which voltage you select. This completes the 
voltage conversion process. 
Circuit protection 
Where the service branch is protected with a fuse or 
circuit breaker that has too high a value to offer 
protection to the motor supplied, a fuse or circuit 
breaker box should be used at the point where the 
machine connection is made and the time delay fuse 
or circuit breaker should be a value just slightly higher 
than the maximum load current draw. 
9.2  Three phase electrical hookup 
1.  Be certain the power to the branch you are 
connecting is off and locked out, so power cannot 
be reestablished accidentally. 
2.  Connect the ground wires. These wires will be 
either green, or green with a white stripe. 
3.  Connect the remaining three cable wires to the 
three power wires in the service branch. 
4.  Reestablish the power to the branch. 
Motor rotation 
The motor should be turning counterclockwise, the 
belt sander should be moving downward and the disc 
sander should be turning clockwise. If this is the case, 
the machine can be considered wired correctly. If the 
motor is not turning in the correct direction, take the 
following corrective action: 
1.  Disconnect power in the branch again and be 
certain it cannot be accidentally turned on while 
you correct the wiring. 
2.  Reverse ANY TWO of the power wires to the 
machine. 
3.  Reestablish the power to the machine. 
4.  Turn the machine on. The motor should now be 
turning in the correct direction.  
Voltage conversion 
Three phase machines are pre-wired for 230V or 
460V per customer request. If it becomes necessary 
to change the voltage: 
1.  Remove back cover from the base and place 
machine on its side.  
2.  Remove terminal cover from motor. Rewire the 
motor according to the motor connection 
diagram in section 12.2.  
3.  Replace the current magnetic switch with the 
460V switch (p/n 4202A-5095, purchased 
separately – see your dealer or contact Walter 
Meier to order). 
4. This completes the voltage conversion 
process. 
Circuit protection 
Where the service branch is protected with a fuse or 
circuit breaker that has too high a value to offer 
protection to the motor supplied, a fuse or circuit 
breaker box should be used at the point where the 
machine connection is made and the time delay fuse 
or circuit breaker should be a value just slightly higher 
than the maximum load current draw.