8.  Maintenance Functions 
8.1  Data Input/Output Function 
 
 
 
III-61
 
8.1.2  Data Output 
 
 (1) 
Explanation 
of 
function 
 
 
When the user PLC is stopped, the various data on the data input/output output screen can be 
converted from HEX to ISO/EIA and output to the external RS-232C device. 
 
 
User PLC stopping operation 
 
 
This function can be used only when the user PLC is stopped.  
 
 
To stop the user PLC, enter the emergency stop state by pressing the emergency stop button, and set 
the rotary switch NCSYS to "1". 
 
Press the "emergency stop" 
button to enter the emergency 
stop state. 
 
RESET 
 
 
 
 
Data group output operation 
Setting area operation 
Output data (No.) 
# (99) DATA  (     ALL1) 
Plain data 
  100~149 
# (99) DATA  (     ALL2) 
File data   
  200~230 
# (99) DATA  (     ALL3) 
PLC program  250~299 
 
 
 
Single data output function 
Setting area operation 
Output data (No.) 
# (99) DATA  (                ) 
Single data    100~149, 200~230, 250~299 
 
 (Note 
1)  If a data No. that is not in the specifications is set, the error message "E06 NO SPEC" will display, 
and the data will not be output. 
 
 
 
  When group output is executed, the data not in the specifications will not be output.