Appendix 2.6 EMC Countermeasure Parts
171
(3)
Example of surge absorber installation
An example of installing the surge absorber in the machine control panel is shown below. 
A short-circuit fault will occur in the surge absorber if a surge exceeding the tolerance is applied. Thus, install a 
circuit protection breaker in the stage before the surge absorber. Note that almost no current flows to the surge 
absorber during normal use, so a breaker installed as the circuit protection for another device can be used for the 
surge absorber. 
Surge absorber installation
 CAUTION
1. The wires from the surge absorber should be connected without extensions. 
2. If the surge absorber cannot be installed just with the enclosed wires, keep the wiring length of A and B to 2m 
or less. If the wires are long, the surge absorber's performance may drop and inhibit protection of the devices 
in the panel. 
3. Surge absorber to be selected varies depending on input power voltage. 
MC
 
 
NC unit
 
Control panel
 
(relay panel,
 etc.)
 
Other device 
(panel power 
supply, etc.)
 
 
Other device 
(panel power 
supply, etc.)
 
 
Panel earth
leakage 
breaker
Input  
power
 
 
AC reactor
 
Transformer
Grounding
Grounding plate
 
Factory power
 
Contactor  
Circuit
protector 
Power supply 
unit 
and 
drive unit
 
 
 
 
 
(1) Surge absorber
     (Protection across phases)
(2) Surge 
absorber
     (Protection across each phase's grounding)
Circuit
protector
Circuit