removed. The third-party meter IDR uses a DIP switch to 
perform this function. This switch is preset at the factory and 
requires no further adjustment.
Fig. 5. Overview of main circuit board.
MAIN CIRCUIT BOARD VISUAL 
CHECKS
Once you have connected meter #1 to jack #1 in the IDR, the 
IDR should be energized. If the IDR is not energized, verify:
1. Meter #1 is turned on. (Meter #1 powers the IDR; if 
Meter #1 is not installed and powered up, the IDR will 
not function.)
2. Verify that JMP8 on the IDR circuit board has a jumper 
installed.
3. Verify that J23 & J24 on the IDR circuit board are set in 
the position labeled “MTR”. Both jumpers should be set 
to the RIGHT position.
4. Verify that the cable between Meter #1 and Jack #1 on 
the IDR is properly assembled. (See Appendix A for 
cable assembly.)
NOTE: If the IDR is being powered by the optional AC 
adapter instead of by Meter #1, see Section 5.0.
Verify the status of the LED indicators on the IDR circuit 
board. (See Appendix B for locations.)
1. Power Supply Indicators
L3, green -> This LED is ON.
L1, green -> This LED is ON.
2. System status indicators
D4 (CPU), red -> This LED flashes once per sec-
ond. If D4 flashes twice per second, the IDR is not 
initialized. This will be addressed later using E-
Mon Energy software.
D7 (Low Battery) -> This LED must be OFF. This 
LED indicates a low or missing battery.
D6 (System Error) -> This LED must be OFF.
3. Meter pulse indicators
Yellow LEDs P1 through P8 may be flashing. 
These LEDs indicate each meter’s pulse rate. 
The flash rate depends on how much load the 
meter is measuring. The faster the pulse the 
greater the load.
IMPORTANT:
IF THE METER MEASURES ZERO LOAD, THERE 
IS NO METER PULSE, WHEN THE PULSE RATE 
IS ZERO THE YELLOW LED INDICATOR WILL 
REMAIN EITHER ON OR OFF UNTIL THERE IS A 
LOAD.
NOTE: If one of the LEDs does not flash, verify the meter 
connection first. If the meter is properly connected, 
check the meter’s display for a flashing load indica-
tor.
4. Panel Indicators
Two LEDs are visible through the window on the 
door of the stand-alone enclosure. THESE LEDS 
ARE NOT PRESENT IN MMU STYLE IDRS.
Green LED (Power Indicator) -> The green LED 
indicates that power is present at the IDR.
Red LED (Tamper Alarm) -> The red LED indi-
cates that the IDR door has been opened. This 
tamper alarm LED will be on when the door is 
closed, and will flash when the door is open. 
When the software startup is performed, the IDR 
will be initialized by the E-Mon Energy software 
and the alarm LED will turn off as long as the door 
remains closed. The alarm can only be reset 
through the software.
5. IDR 16 Option 16 Card (applies only to the SUBIDR-16 
model.)
For each meter (9-16) installed on the options 
card, another set of yellow LEDs (P9-P16) will be 
present. These LEDs indicate the meter pulse 
rate for meters #9 through #16.
OPTIONAL AC ADAPTER 
(OPTIONAL EXTERNAL 120 VAC 
POWER SUPPLY)
If you are NOT using the optional AC adapter to power the 
IDR, proceed to Section 6.0.
Instead of powering the IDR using Meter #1, Honeywell can 
supply an optional AC adapter. If the IDR was provided with 
this option, verify the following:
1. Jumpers J23 & J24 on the IDR circuit board are set to 
the LEFT position (position labeled “EXT”.)
2. Jumper at JMP8 MUST be removed.
3. The AC adapter’s two-wire cord must be plugged into 
the IDR at TB9. (The polarity of these wires does not 
matter.)
4. Plug the AC adapter into a 120 VAC outlet.