Seagate ST240HM001 ユーザーズマニュアル

ページ / 39
S
EAGATE 
600 SSD P
RODUCT 
M
ANUAL
, R
EV
. B
  19
  
3.5
C
OOLING 
Cabinet cooling must be designed by the  customer so that the ambient temperature immediately surrounding the drive will 
The rack, cabinet, or drawer environment for the drive must  provide heat removal. You should confirm that adequate heat 
the drive should be oriented, or air flow directed, so that the least amount of air flow resistance is created while providing air 
flow to the drive. Also, the shortest possible path between the air inlet and exit should be chosen to minimize the travel length 
of air heated by the drive and other heat sources within the rack, cabinet, or drawer environment.
by one or more fans, either forcing or drawing air as shown in  the illustrations. Conduction, convection, or other forced air-
Figure 5. 
Air flow
Image may not represent actual product, for reference only.
Above unit
Under unit
ote. Air flows in the direction shown (back to front)
or in reverse direction (front to back)
Above unit
Under unit
ote. Air flows in the direction shown or
in reverse direction (side to side)