Appendix B.  Trouble Shooting/Connections - Tips and Hints 
Appendix B.1. 
Connection problems. 
Confirm that the device you are trying to attach to the FieldServer is in fact a DataPort device and not 
a DataLink device which looks very similar but connects differently. 
A DataLink device  will require the DataLink driver –  FieldServer part # FS-8700-82.  Please contact 
FieldServer to request an exchange of driver. 
Appendix B.2. 
Timeouts 
Some Data Port tables are long and result in messages of up to 6.5 kB being sent from the data port 
to the FieldServer. The default timeout is insufficient in such cases. 
 
In resolving one customer’s connection problems a timeout of 4 s on a table of 134 entries was found 
to produce good results. 
 
Please read the notes provided with Error message #25 in section Appendix D of this manual. 
 
Appendix B.3. 
Determining Storage Locations 
Set the Application parameter to ‘Print_storage_locations’ on the connection to tell the driver to print 
messages each time it stores data.  The driver dumps messages in the error log reporting the Data 
Array name, offset, value and the ‘line’ from which the data was extracted. 
 
Remove the parameter to stop the messages being printed. 
 
Example:  
 
In the line below the driver reports that the line beginning ‘hd_pos_a…..’ was processed and that the 
value 0.0 was stored in DA_D2_01 at offset 149. 
 
T02> DPStore:DA=DA_D2_01 Off=49 Val=0.00 <hd_pos_a 0.0 
T02>   See above===>hd_pos_a 0.0        003 000 Head Press A