Fujitsu DX80 S2 ユーザーズマニュアル
Chapter 1 Hardware Configurations
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED
P3AM-4822-12ENZ0
25
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.8 Power distribution unit (AC200-240V, 1U, Max 2 enclosures connection) and provided AC cable
specifications
■
Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 6 enclosures
connection)
There are 12 outlets.
Figure 1.24 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection)
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.9 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection) and provided AC cable
specifications
Item
Specifications
Power
Voltage
AC200 - 240V
Phase
Single
Frequency
50Hz/60Hz
Input cable
Connection type
IEC60320-C13 ↔ NEMA L6-15P
Length
4m
Quantity
2
Output cable
Connection type
IEC60320-C13 ↔ IEC60320-C14
Length
3m
Quantity
4
Item
Specifications
Power
Voltage
AC200 - 240V
Phase
Single
Frequency
50Hz/60Hz
Input cable
Connection type
Straight-through ↔ NEMA L6-20P
Length
4m
Quantity
2
Output cable
Connection type
IEC60320-C13 ↔ IEC60320-C14
Length
3m
Quantity
12
Outlets (OUTPUT)