I/O Terminal Descriptions
Note:
The programmable terminal assignments of the discrete input terminals may be 
accessed and changed from their default settings as mapped on 
 (see Input 
Terminals).
ST — The default setting for this terminal is ST. The function of this input as ST is a Standby mode 
controller (system is in Standby when on). As the default setting, this terminal must be connected to 
CC for normal operation. If not connected to CCOff is displayed on the LCD screen. This input 
terminal may be programmed to any 1 of the 69 functions that are listed in 
. See 
 for more information on this terminal.
RES — The default setting for this terminal is RES. The function of this input as RES is a system 
Reset. A momentary connection to CC resets the ASD and any fault indications from the display. This 
input terminal may be programmed to any 1 of the 69 possible functions that are listed in 
Reset is effective when faulted only. Se
 for more information on 
this terminal.
F — The default setting for this terminal is Forward RunForward Run runs the motor in the 
Forward direction when it is on. This input terminal may be programmed to any 1 of the 69 functions 
that are listed in 
. See 
 for more information on this terminal.
R — The default setting for this terminal is Reverse RunReverse Run runs the motor in the Reverse 
direction when it is on. This input terminal may be programmed to any 1 of the 69 functions that are 
listed in 
. See 
 for more information on this terminal.
S1 — The default setting for this terminal is S1. The function of this input as S1 is to run the motor at 
Preset Speed #1 (see 
) when it is on. This input terminal may be 
programmed to any 1 of the 69 functions that are listed in 
. See 
 for more information on this terminal.
S2 — The default setting for this terminal is S2. The function of this input as S2 is to run the motor at 
Preset Speed #2 (see 
) when it is on. This input terminal may be 
programmed to any 1 of the 69 functions that are listed in 
. See 
 for more information on this terminal.
S3 — The default setting for this terminal is S3. The function of this input as S3 is to run the motor at 
Preset Speed #3 (see 
) when it is on. This input terminal may be 
programmed to any 1 of the 69 functions that are listed in 
. See 
 for more information on this terminal.
S4 — The default setting for this terminal is Emergency Off (normally closed). The function of this 
input as Emergency Off is to remove power from the output of the ASD and may apply a supplemental 
braking system using the method selected at the Emg Off Mode selection parameter. This input 
terminal may be programmed to any 1 of the 69 functions that are listed in 
. Se
 for more information on this terminal.
RR — The default function assigned to this terminal is to carry out the Frequency Mode #1 setting. 
The RR terminal accepts a 0 – 10 VDC input signal and controls the function assigned to this terminal. 
This input terminal may be programmed to control the speed or torque of the motor. It may also be used 
to regulate (limit) the speed or torque of the motor. The gain and bias of this terminal may be adjusted 
for application-specific suitability.
 
See 
 for more 
information on this terminal.
RX — The RX terminal accepts a ±10 VDC input signal and controls the function assigned to this 
terminal. This input terminal may be programmed to control the speed, torque, or direction of the motor. 
It may also be used to regulate (limit) the speed or torque of the motor. The gain and bias of this 
terminal may be adjusted for application-specific suitability.
 
See 
 for more information on this terminal.