2. Installation
RuggedCom® RuggedPower™
11
RP100 Installation Guide Rev100
2.4.2. RuggedMAX Power Port / IEEE802.3at Port
The RuggedMax Power port takes data received on the 10/100 Base TX port and injects power
on pins 4, 5 and 7, 8. CAT-5E STP (shielded twisted pair) cable should be used to connect this
port to the powered device. For RP100 units with the “AT” IEEE802.3at-compliance option, the
unit only delivers power when an IEEE802.3at-compliant powered device is attached.
Figure 2.4. RJ45 Port Pinout
RuggedMax Power
10/100 Base Tx
Pin
Signal
Pin
Signal
1
+Tx
1
+Tx
2
-Tx
2
-Tx
3
+Rx
3
+Rx
4
V+
4
Terminated
5
V+
5
Terminated
6
-Rx
6
-Rx
7
V-
7
Terminated
8
V-
8
Terminated
Case
Shield (Chassis
Ground)
Case
Shield (Chassis
Ground)
Table 2.1. RJ45 Ethernet Port Pinout
The unused pins, 4, 5, 7, and 8 of the 10/100Tx port are terminated to Chassis Ground
via a network that improves EMI and ESD performance.