Digital Modules
4-64
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications
 
of the SM 422; DO 16 
 
 24 VDC/2 A
Dimensions and Weight
Dimensions W 
 
 H 
 
 D  
(in millimeters)
25 
 
 290 
 
 210
Weight
Approx. 600 g
Data for Specific Module
Number of outputs
16
Length of cable
Unshielded
Shielded
600 m
1000 m
Voltages, Currents, Potentials
Power rated voltage of the
electronics L+
24 VDC
Rated load voltage L+
24 VDC
Aggregate current of
the outputs (two outputs
per supply group 
1)
)
Up to 40 
C
Up to 60 
C
Max. 3 A
Max. 2 A
Isolation
Between channels and
backplane bus
Yes
Between the channels
In groups of
Yes
8
Permitted potential difference
Between the different
circuits
75 VDC / 60 VAC
Insulation tested with
Channels against
backplane bus and load
voltage L+
500 VDC
Between the outputs of the
different groups
500 VDC
Current consumption
From the backplane bus
 Power supply and load
voltage L+ (no load)
Max. 160 mA
Max. 30 mA
Power dissipation of the
module
Typ. 5 W
Status, Interrupts, Diagnostics
Status display
Green LED per
channel
Interrupts
None
Diagnostic functions
None
Data for Selecting an Actuator
Output voltage
At signal “1”
Min. L+ (-0,5 V)
Output current
At signal “1”
Rated value
2A
Permitted range
5 mA to 2.4 A
At signal “0” (leakage
current)
Max. 0.5 mA
Output delay (for resistive load)
From “ 0” to “1”
Max. 1 ms
At “1” to “0”
Max. 1 ms
Load resistor range
24 
 to 4 k
Lamp load
Max. 10 W
Parallel connection of 2 
outputs
For redundant triggering of
a load
Possible (only outputs
of the same group)
To increase performance
Not possible
Triggering a digital input
Possible
Switch rate
For resistive load
For inductive load to IEC
947-51, DC 13
100 Hz
0.2 Hz at 1 A
0.1 Hz at 2A
For lamp load
Max. 10 Hz
Limit (internal) of the inductive
circuit interruption voltage up to
Max. -30 V
Short-circuit protection 
of output
1
Threshold on
Electronically cyclic
2)
2.8 A to 6 A
1) A supply group always consists of two adjacent
channels starting with channel 0. Channels 0 and 1, 2
and 3 and so on up to 14 and 15 therefore form one
supply group.
2) Following a short circuit, reclosing under a full load is 
not guaranteed. To prevent this, you can do one of the 
following things:
Change the signal at the output, or
Interrupt the load voltage of the module
Briefly disconnect the load from the output