Siemens M7-400 ユーザーズマニュアル

ページ / 638
Digital Modules
4-85
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 422; DO 16 
 
 120/230 VAC/2 A
Programming package
Associated programming
package
As of STEP 7 V 2.0
Dimensions and Weight
DimensionsW 
 
 H 
 
 D
(in millimeters)
25 
 
 290 
 
 210
Weight
Approx. 800 g
Data for Specific Module
Number of outputs
16
Length of cable
Unshielded
Shielded
600 m
1000 m
Voltages, Currents, Potentials
Rated load voltage L1
Permitted frequency range
79 to 264 VAC
47 to 63 Hz
Total current of the outputs (per
group)
Up to 40 
C
Up to 60 
C
With fan subassembly
Max. 4 A
6 A
Max. 2 A
5 A
Isolation
Between channels and
backplane bus
Yes
Between the channels
In groups of
Yes
4
Permitted potential difference
Between the outputs of the
different groups
500 VAC
Insulation resistance
4000 VAC
Current consumption
From the backplane bus
From load voltage L +
(without load)
Max. 400 mA
1.5 mA
Power dissipation of the
module
Typ. 16 W
Status, Interrupts, Diagnostics
Status display
Green LED per
channel
Interrupts
None
Diagnostic functions
Parameters cannot be
assigned
Group error display
For internal fault
Red LED (INTF) 
failed fuse
For external fault
Red LED (EXTF)
failed load voltage
Data for Selecting an Actuator
Output voltage
At signal “1”
At maximum current
min. L1 (–1.3 Vrms)
At minimum current
min. L1 (–18.1 Vrms)
Output current
At signal “1”
Rated value
2 A
Permitted range
10 mA to 2 A
Permitted surge current
(per group)
Max. 50 A per cycle
At signal “0” (leakage
current)
Max. 2.6 mA
Output delay (for resistive load)
From “ 0” to “1”
Max. 1 ms
At “1” to “0”
Not more than 1 AC
scan cycle
Minimum load current
10 mA
Zero cross inhibit voltage
Non-zero cross outputs
Size of the motor starter
Max. size 5 to NEMA
Lamp load
Max. 50 W
Parallel connection of 2 
outputs
For redundant triggering of
a load
Possible (only outputs
connected to the same
load)
Triggering a digital input
Possible
Switch rate
For resistive load
Max. 10 Hz
For inductive load, to 
IEC 947-5-1, AC 15
Max. 0.5 Hz
For lamp load
1 Hz
Short-circuit protection of the
output
Fuse, 8 A, 250 V (per
group)
Min. current required for
fuse to blow
Min. 100 A
Max. response time
Max. 100 ms
Replacement fuses
Wickmann
Schurter
Littelfuse
Fuse, 8 A, quick-acting
194-1800-0
SP001.1013
217.008