Siemens M7-400 ユーザーズマニュアル

ページ / 638
Analog Modules
5-82
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Status, Interrupts, Diagnostics
Interrupts
None
Diagnostic functions
None
Substitute value can be applied
No
Data for Selecting a Sensor
Input range (rated values)/Input
resistance
Voltage
"
 80 mV/1 M
"
 250 mV/1 M
"
 500 mV/1 M
"
 1 V/1 M
"
 2.5 V/1 M
"
 5 V/1 M
1 to 5 V
1 M
"
 10 V/1 M
Current
0 to 20 mA
50 
"
 20 mA/50 
4 to 20 mA
50 
Resistors
0 to 48 
1 M
0 to 150 
1 M
0 to 300 
1 M
0 to 600 
1 M
0 to 6000 
1 M
(can be used up to
5000 
)
Thermocouples
TC type B/1 M
TC type R/1 M
TC type S/1 M
TC type T/1 M
TC type E/1 M
TC type J/1 M
TC type K/1 M
TC type U/1 M
TC type L/1 M
TC type N/1 M
Resistance thermometer
Pt 100/1 M
Pt 200/1 M
Pt 500/1 M
Pt 1000/1 M
Ni 100/1 M
Ni 1000/1 M
Maximum input voltage for
voltage input (destruction limit)
Max. 18 V continuous
75 V for 1 ms (cycle
factor 1 : 20)
Maximum input current for
current input (destruction limit)
40 mA continuous
Connection of the sensor
For measuring voltage
Possible
For measuring current
As two-wire transmitter
Possible
As four-wire
transmitter
Possible
For measuring resistance
With two-conductor
terminal
Possible; cable
resistance is also
measured
With three-conductor
terminal
Possible
With four-conductor
terminal
Possible
Load of the two-wire
transmitter
Max. 750 
Characteristic linearization
Parameters can be
assigned
For thermocouples
Types B, R, S, T, E, J,
K, U, L, N
For 
resistance thermometers
Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100, 
Ni 1000
Temperature compensation
Yes, programmable
Internal temperature
compensation
No
External temperature
compensation with
compensating box
Possible
External temperature
compensation with Pt 100
Possible
Compensation for
definable reference
junction
temperature
Possible
Unit for temperature
measurement
Degrees Celsius