Siemens M7-400 ユーザーズマニュアル

ページ / 638
Analog Modules
5-118
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Example
If you have select “current (two-wire transmitter)” for channel 6, you can only
disable the measuring method or set “current (two-wire transmitter)” for channel 7.
Circuit for Resistance and Temperature Measurement
The following conditions apply when measuring the resistance and temperature
with the SM 431; AI 16 x 16 Bit:
Table 5-67 Channels for Resistance and Temperature Measurement of the SM 431; AI 16 
 
 16 Bit
Measuring Type Parameter
Permissible
for Channel n
Condition
Resistor 
(four-conductor terminal)
0, 2, 4, 6, 8, 10,
12 or 14
You must disable the 
(
“Measuring Type” parameter
for channels n+1 (1, 3, 5, 7, 9, 11, 13, 15).
Resistor 
three-conductor terminal
0, 2, 4, 6, 8, 10,
12 or 14
( , , , , ,
,
,
)
The reason The connections of channel n+1 are used
to supply the resistance that is connected to channel
Thermal resistor
(linear, four-conductor termi-
nal)
0, 2, 4, 6, 8, 10,
12 or 14
pp y
n.
Thermal resistor
(linear, four-conductor termi-
nal)
0, 2, 4, 6, 8, 10,
12 or 14
Thermocouple (linear)
0 to 15
You can select the reference junction. It is only
advisable to specify a reference junction with
thermocouples.
Circuit for Reference Junction Compensation for Thermocouples
If you select “RTD on Channel 0” as a reference junction for reference junction
compensation for thermocouples, the following applies:
Table 5-68 Reference Junction Compensation via RTD on Channel 0 of the SM 431; AI 16 
 
 16 Bit
Reference Junction
Parameter
Permissible
for
Channel n
Condition
RTD on Channel 0
2 to 15
You must connect and parameterize on channel 0 a
resistance thermometer with linearization, a 3- or
4- conductor terminal in climatic range. This means that
channels 0 and 1 are assigned.
The reason If channel 0 is to be used as the reference
junction, a resistance-type sensor must be connected
there to establish the absolute temperatures in the
climatic range.