Interface Submodules
13-39
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
A5E00069467-07
Non-Isolated Measured Value Sensors
Potential differences must not arise between non-isolated measured value sensors.
If necessary, you must take additional installation measures (equipotential bonding
conductor) to ensure this.
If necessary, you must take additional installation measures (equipotential bonding
conductor) to ensure this.
Figure 13-14 shows the connection of non-isolated measured value sensors.
+
-
V
E0
Non-isolated
measured value
sensors
measured value
sensors
Ground bus
+
-
V
E1
M
SENSOR
MV
0+
M
0-
MV
1+
M
1-
Figure 13-14 Connection of Non-Isolated Measured Value Sensors
Connection of Voltage Sensors
Figure 13-15 shows the connection of voltage sensors to the analog input module.
+
-
U
+
-
U
+24 V
MV
0+
M
0-
MV
1+
M
1-
M
L+
V
CM1
V
CM0
0 V
Figure 13-15 Connection of Voltage Sensors