8  Bus Parameters for PROFIBUS TM System Bus on ASx88/TM
and WinCC
 
Parameter
description
 
DOS_CONF.DAT
 
in AS488 and
Bridge
 
L2AMPRO.INI
in
 
ASx88
 
Configura-
tion dialog in
Windows NT
for WinCC
 
Value
 
Highest station address
 
l2_hsa
 
l2_hsa
 
Highest Sta-
tion Address
 
1 .... 126
 
Local device address
 
l2_ts
 
l2_ts
 
Local Station
Address
 
1 .... 99
 
Baud rates (index)
 
l2_baud_rate
 
l2_baud_rate
 
Transmission
Rate
 1,5 Mbits/s
 
Slot time
 
l2_tsl
 
l2_tsl
 
Tslot
 
3000
 
Quiet time
 
l2_tqui
 
l2_tqui
 
Tqui
 
0
 
Setup time
 
l2_tset
 
l2_tset
 
Tset
 
240
 
Minimum station delay
time
 
l2_max_tsdr
 
l2_max_tsdr
 
Max Tsdr
 
980
 
Maximum station delay
time
 
l2_min_tsdr
 
l2_min_tsdr
 
Min Tsdr
 
150
 
Token rotation time
 
l2_ttr
 
l2_ttr
 
Ttr
 
min.
90000  *)
 
GAP factor
 
l2_g
 
l2_g
 
Gap factor
 
30    **)
 
Call repetitions
 
l2_retry_ctr
 
-
 
Retry Limit
 
1
 
Ready time
 
-
 
-
 
Trdy
 
150
 
Idle time 1
 
-
 
-
 
Tid1
 
515
 
Idle time 2
 
-
 
-
 
Tid2
 
980
 
 
The PROFIBUS bus parameters for WinCC are specified in the user-defined profile. But for the Ttr parame-
ter, the values of the general-purpose profile will be transferred to the user-defined profile if the general-
purpose profile is selected beforehand. In this case, these values are almost identical to the above-
mentioned ones.
 
 
*) Use the following formula to calculate the Ttr parameter, and enter it:
Ttr (l2_ttr) = 9000 * [number of active PROFIBUS-TM devices].
 
Note: The factor 9000 in the formula is only valid for a baud rate of 1.5 Mbits/s.
 
 
**) For the baud rate of 1.5 Mbits/s, the default value of the gap factor is 30 – 50. Entering a smaller value
may be necessary in exceptional cases.
 
 
All specified bus parameters are tuned to the baud rate of 1.5 Mbits/s. Any change/optimization requires a
deep knowledge of the PROFIBUS standard.
 
 
The bus parameters for all TELEPERM components (e.g. OS525 and PROGRAF AS) on the PROFIBUS TM
system bus must be selected accordingly.