Omron C200HX ユーザーズマニュアル

ページ / 564
464
10-3-7 AR AREA READ –– RJ
Reads the contents of the specified number of AR words, starting from the speci-
fied word.
Command Format
@
R
J
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
Terminator
Beginning word
(0000 to 0027)
Node no.
Header
code
No. of words
(0001 to 0028)
Response Format
@
R
J
FCS
x 10
1
x 10
0
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
Node no.
End code
Header
code
Read data (1 word )
Read data 
(for number of words read)
Terminator
Limitations
The text portion of the response’s first frame can contain up to 30 words.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect and an end code of 15 (entry number data error) will be returned if the
specified words exceed the data area boundaries or aren’t specified in BCD.
End code
Contents
00
Normal completion
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
10-3-8 EM AREA READ –– RE
Reads the contents of the specified number of EM words, starting from the spe-
cified word in the specified EM bank.
Command Format
@
R
E
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
Node no.
Header
code
Terminator
Beginning word
(0000 to 6143)
No. of words
(0001 to 6144)
Bank no.
(See note.)
Bank No.
Note Input 00, 01, or 02 to specify bank number 0, 1, or 2. Input two spaces to specify
the current bank.
Host Link Commands