Omron C200HX ユーザーズマニュアル

ページ / 564
480
End code
Contents
04
Address over
13
FCS error
14
Format error
15
Entry number data error
16
Command not supported
18
Frame length error
23
User memory protected
10-3-22
SV CHANGE 3 –– W%
Changes the contents of the second word of the TIM, TIMH(15), CNT,
CNTR(12), or TTIM(87) at the specified program address in the user’s program.
Command Format
@
W
%
OP4
OP3
OP2
OP1
x 10
2
x 10
0
x 10
1
x 10
5
x 10
4
x 10
3
x 10
0
x 10
3
x 10
2
x 10
1
x 10
1
x 10
0
OP4
OP3
OP2
OP1
x 10
2
x 10
3
x 10
1
x 10
0
Node no.
Program
address
Must be “0”
Mnemonic
Timer/counter
(0000 to 0511)
Terminator
FCS
Header
code
Operand
SV
Use all four characters to specify the timer or counter instruction’s mnemonic.
Add a space to the end of a TIM or CNT mnemonic to make it 4 characters long.
Instruction name
Mnemonic
TC number
OP1
OP2
OP3
OP4
range
TIMER
T
I
M
(Space) 0000 to 0511
HIGH-SPEED TIMER
T
I
M
H
COUNTER
C
N
T
(Space)
REVERSIBLE COUNTER
C
N
T
R
TOTALIZING TIMER
T
T
I
M
The “Operand” parameter indicates the data area where the SV is stored or a
constant. The “SV” parameter indicates the word address or the SV itself if it is a
constant.
Operand
Classification
Constant or
OP1
OP2
OP3
OP4
word address
C
I
O
(Space)
IR or SR
0000 to 0511
L
R
(Space)
(Space)
LR
0000 to 0063
H
R
(Space)
(Space)
HR
0000 to 0099
A
R
(Space)
(Space)
AR
0000 to 0027
D
M
(Space)
(Space)
DM
0000 to 6655
D
M
(Space)
DM (indirect)
0000 to 6655
C
O
N
(Space)
Constant
0000 to 9999
E
M
(Space)
(Space)
EM
0000 to 6143
E
M
(Space)
EM (indirect)
0000 to 6143
Host Link Commands