Omron C200HX ユーザーズマニュアル

ページ / 564
494
End code
Contents
14
Format error
15
Entry number data error
18
Frame length error
19
Not executable
23
User memory protected
A3
Aborted due to FCS error in transmit data
A4
Aborted due to format error in transmit data
A5
Aborted due to entry number data error in transmit data
A8
Aborted due to frame length error in transmit data
10-3-34
I/O TABLE GENERATE –– MI
Corrects the registered I/O table to match the actual I/O table.
Command Format
@
M
I
x 10
0
x 10
1
Node no.
Header
code
Terminator
FCS
Response Format
@
M
I
x 10
0
x 10
1
x 16
1
x 16
0
Node no.
Header
code
End code
Terminator
FCS
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
---
---
OK
---
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
End code
Contents
00
Normal completion
01
Not executable in RUN mode
02
Not executable in MONITOR mode
03
UM write-protected
13
FCS error
14
Format error
18
Frame length error
20
Couldn’t create I/O table
Note The write-protected error code for this command is different from the other com-
mands.
Host Link Commands
Section 10-3