SITRANS LU01 – INSTRUCTION MANUAL
Page 35
m
mmmm
Pa
ra
m
e
te
rs
Entering a Level Breakpoint
1.
Go to Parameter P054.
2.
Press  
 to display the index symbol.
3.
For each index enter a volume.
4.
Ensure that each volume corresponds to the same index for P055.
5.
Press .
For more on Volume Characterization, go to page 87.
P055 Volume Breakpoints and Characterization 
(Universal Volume Calculation) 
Each segment defined by the level breakpoints (P055) requires a volume so that the 
SITRANS LU01 can make the level-to-volume calculations.
Typical volume calculations
Entering a Volume Breakpoint
1.
Go to Parameter P055.
2.
Press  
 to display the index symbol.
3.
For each index enter a volume.
4.
Ensure that each volume corresponds to the same index for P054.
5.
Press .
For more on Volume Characterization, go to page 87.
Primary Index
Breakpoint
Values
Range: 0.0 to 9999
Related
P054 Breakpoints Levels (Universal Volume Calculation)
Cone
Cylinder
V = (1/3)πr
2
h
V  =  πr
2
h