SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
If the timer expires (before a valid measurement is made), the SITRANS LU01 advances to 
the Failsafe Material Level (P071) as restricted by Failsafe Advance (P072).
When a valid measurement is made after the timer expires, the SITRANS LU01 advances 
to the new material level (if changed), as restricted by Failsafe Advance (P072) and the 
timer resets. 
If the timer expires due to a measurement difficulty, LOE flashes in the Reading display.
Once activated, the Failsafe State initiates the following:
1.
The material level is reported based on P071 Failsafe Material Level.
• The unit responds to the new level as programmed (control and alarm relays 
activate as defined by the programming).
• Individual relays can have independent failsafe responses. See 
P129 Relay 
Failsafe
.
2.
The appropriate error is displayed:
• LOE for loss of echo from the transducer
• Short for a shorted transducer cable
• Open for a cut transducer cable or a defective transducer
• Error for all other problems including reversed Ultrasonic/Temperature 
transducer terminal connections or wrong Transducer (P004) entered. 
When modifying the preset value, set it short enough to protect the process but long 
enough to avoid false alarms. Only use No Delay (0.0 Minutes) for testing.
P071 Failsafe Material Level
The material level reported when a Failsafe State is initiated.
Select the Failsafe Material Level based upon the relay operation required during failsafe 
operation.
Selecting HI, LO, or HOLd
1.
Press FUNCTION 
 to display the Auxiliary Function symbol.
2.
Press ARROWS 
 
 to scroll to the desired option.
3.
Press ENTER 
 to set the value.
Values
Range: -999 to
9999
Value in units or % (-50% to 150% of span)
HI
Level goes to maximum span
LO
Level goes to 0 span (Empty)
HOLd
*
Level remains at last reading
Related
P001  Operation
P006  Empty
P007  Span
P111 Relay Control Function
P112 Relay ON Setpoint
P113 relay OFF Setpoint
P129  Relay  Failsafe