Mitsubishi Electronics Q02HCPU ユーザーズマニュアル

ページ / 236
 
 
 
11 - 43                                                                                                                                                       11 - 43 
MELSEC-Q
 
11   TROUBLESHOOTING 
 
Special Relay List 
(1) Diagnostic Information 
 
Number
 
Name
 
Meaning
 
Explanation
 
Set by 
(When Set)
 
Corresponding 
ACPU 
M9 
 
 
 
Applicable 
CPU 
SM0 Diagnostic 
errors 
OFF : No error 
ON : Error 
• ON if diagnosis results show error occurrence  
(Includes when an annunciator is ON, and when an error 
is detected with CHK instruction) 
• Stays ON subsequently even if normal operations 
restored 
S (Error) 
New 
SM1 
Self-diagnosis 
error 
OFF : No self-diagnosis 
errors 
ON : Self-diagnosis 
• Comes ON when an error occurs as a result of self-
diagnosis. (Does not include when annunciator is ON or 
when error is detected by CHK instruction.) 
• Stays ON subsequently even if normal operations 
restored 
S (Error) 
M9008 
SM5 
Error common 
information 
OFF : No error common 
information 
ON  : Error common 
information 
• When SM0 is ON, ON if there is error common 
information 
S (Error) 
New 
SM16 
Error individual 
information 
OFF : No error common 
information 
ON  : Error common 
information 
• When SM0 is ON, ON if there is error individual 
information 
S (Error) 
New 
SM50 Error 
reset 
OFF 
ON : Error reset 
• Conducts error reset operation 
New 
+Rem 
SM51 
Battery low latch 
OFF :  Normal 
ON  : Battery low 
• ON if battery voltage at CPU module or memory card 
drops below rated value.  Stays ON subsequently even 
after normal operation is restored 
• Synchronous with BAT. ALA/BAT. LED 
S (Error) 
M9007 
SM52 Battery 
low 
OFF :  Normal 
ON  : Battery low 
• Same as SM51, but goes OFF subsequently when 
battery voltage returns to normal. 
S (Error) 
M9006 
• Comes ON it a momentary power interruption of less 
than 20ms occurred during use of the AC power supply 
module, and reset by turning the power OFF, then ON. 
 
• Comes ON if a momentary power interruption of less 
than 10ms occurred during use of the DC power supply 
module, and reset by turning power OFF, then ON. 
QCPU 
SM53 
AC/DC DOWN 
detection 
OFF : AC/DC DOWN not 
detected 
ON  : AC/DC DOWN 
detected 
• Comes ON if a momentary power interruption of less 
than 1ms occurred during use of the DC power supply 
module, and reset by turning power OFF, then ON. 
S (Error) 
M9005 
QnA 
SM54 
MINI link errors 
OFF :  Normal 
ON : Error 
• Goes ON if MINI (S3) link error is detected at even one of 
the installed MELSECNET/MINI master modules. 
Stays ON subsequently even after normal operation is 
restored. 
S (Error) 
M9004 
QnA 
SM56 Operation 
Errors 
OFF :  Normal 
ON  : Operation error 
• ON when operation error is generated 
• Stays ON subsequently even if normal operations 
restored 
S (Error) 
M9011 
 
SM60 
Blown fuse 
detection 
OFF :  Normal 
ON  : Module with blown fuse 
• Comes ON even if there is only one output module with a 
blown fuse, and remains ON even after return to normal 
• Blown fuse status is checked even for remote I/O station 
output modules. 
S (Error) 
M9000 
SM61 
I/O module 
verification error 
OFF :  Normal 
ON : Error 
• Comes ON if there is a discrepancy between the actual 
I/O modules and the registered information when the 
power is turned on 
• I/O module verification is also conducted for remote I/O 
station modules. 
S (Error) 
M9002 
+Rem 
SM62 
Annunciator 
detection 
OFF : Not detected 
ON : Detected 
• Goes ON if even one annunciator F goes ON. 
(Instruction 
execution) 
M9009 
SM80 CHK 
detection 
OFF : Not detected 
ON : Detected 
• Goes ON if error is detected by CHK instruction.
 
• Stays ON subsequently even after normal operation is 
restored. 
(Instruction 
execution) 
New 
SM90 
Corresponds to SD90 
M9108 
SM91 
Corresponds to SD91 
M9109 
SM92 
Corresponds to SD92 
M9110 
SM93 
Corresponds to SD93 
M9111 
SM94 
Corresponds to SD94 
M9112 
SM95 
Corresponds to SD95 
M9113 
SM96 
Corresponds to SD96 
M9114 
SM97 
Corresponds to SD97 
New 
SM98 
Corresponds to SD98 
New 
SM99 
Startup of 
watchdog timer 
for step transition 
(Enabled only 
when SFC 
program exists) 
OFF : Not started 
(watchdog timer reset) 
ON : Started 
(watchdog timer 
started) 
Corresponds to SD99 
• Goes ON when measurement of 
step transition watchdog timer is  
commenced. 
• Resets watchdog timer when it 
goes OFF. 
New