Mitsubishi Electronics Q25HCPU ユーザーズマニュアル

ページ / 236
 
 
 
11 - 20                                                                                                                                                       11 - 20 
MELSEC-Q
 
11   TROUBLESHOOTING 
 
 
 
 
 
 
 
 
 
 
 
Error Code 
(SD0)
 
Error Contents and Cause 
Corrective Action
 
Corres-
ponding 
CPU
 
 1000 
 
 1001 
 1002 
 1003 
 1004 
QCPU
 
 
1005 
QCPU 
Rem 
 1006 
 1007 
 1008 
Run mode suspended or failure of main CPU module 
(1) Malfunctioning due to noise or other reason 
(2) Hardware fault 
 
1009 
Failure of the power supply module, CPU module, main base unit, 
extension base unit or extension cable is detected. 
(1) Measure noise level. 
(2) Reset and establish the RUN status again. 
If the same error is displayed again, this suggests a CPU 
module hardware error. Contact your nearest Mitsubishi 
representative.
 
QCPU
 
 1010 
 1011 
 
1012 
Entire program was executed without the execution of an END 
instruction. 
(1) When the END instruction is executed it is read as another 
instruction code, e.g. due to noise. 
(2) The END instruction has been changed to another instruction 
code somehow. 
(1) Measure noise level. 
(2) Reset and establish the RUN status again. 
If the same error is displayed again, this suggests a CPU 
module hardware error. Contact your nearest Mitsubishi 
representative.
 
 
 
1101 
Error in internal RAM/program memory where CPU module 
sequence program is stored. 
 
1102 
Error in RAM used as CPU module work area. 
 
1103 
Internal CPU module device error. 
 
1104 
RAM Address error in CPU module. 
This suggests a CPU module hardware error. Contact your nearest 
Mitsubishi representative. 
 
 
1105 
CPU shared memory fault 
(1) Measure noise level. 
(2) Reset and establish the RUN status again. 
If the same error is displayed again, this suggests a CPU 
module hardware error. Contact your nearest Mitsubishi 
representative.
 
QCPU 
function 
Ver. B 
or later 
 
1200 
The circuit that performs CPU internal index modification is not 
operating properly. 
 
1201 
Internal CPU module hardware (logic) does not operate normally. 
 
1202 
The circuit that executes sequence processing in the CPU module 
does not operate properly. 
This suggests a CPU module hardware error. Contact your nearest 
Mitsubishi representative. 
 
 
1203 
The operation circuit that conducts index modification in the CPU 
module is not operating properly. 
 
1204 
The hardware (logic) in the CPU us not operating properly. 
 
1205 
The operation circuit that conducts sequence processing in the CPU 
in not operating properly. 
 
1206 
The DSP operation circuit in the CPU is not operating properly. 
This suggests a CPU module hardware error. Contact your nearest 
Mitsubishi representative. 
Q4AR 
There is an output module with a blown fuse. 
(1) Check ERR. LED of the output modules and replace the module 
whose LED is lit. 
(2) Read the common error information with the peripheral device 
and replace the fuse at the output module corresponding to the 
numerical value (module No.) reading. 
Alternatively, monitor special registers SD1300 to SD1331 with 
the peripheral device and change the fuse of the output module 
whose bit has a value of "1". 
QCPU 
Rem 
There is an output module with a blown fuse. 
(1) Check ERR. LED of the output modules and replace the fuse of 
the module whose LED is lit. 
(2) Read the common error information with the peripheral device 
and replace the fuse at the output module corresponding to the 
numerical value (module No.) reading. 
Alternatively, monitor special registers SD1300 to SD1331 with 
the peripheral device and change the fuse of the output module 
whose bit has a value of "1". 
QnA 
Q4AR 
 
1300 
(1) There is an output module with a blown fuse. 
(2) External power supply for output load is turned off or 
disconnected. 
(1) Check ERR. LED of the output modules and replace the module 
whose LED is lit. 
(2) Read the common error information with the peripheral device 
and replace the fuse at the output module corresponding to the 
numerical value (module No.) reading. 
Alternatively, monitor special registers SD1300 to SD1331 with 
the peripheral device and change the fuse of the output module 
whose bit has a value of "1".  
(3) Check whether the external power supply for output load is ON 
or OFF. 
Q2AS 
 
1310 
An interruption has occurred although there is no interrupt module. 
One of the individual modules is experiencing hardware problems, 
so check the modules. Contact your nearest Mitsubishi 
representative and explain the problem with the defective module. 
 
 
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.