Error Code 
(SD0)
 
Error Contents and Cause 
Corrective Action
 
Corres-
ponding 
CPU
 
 
6100 
A CPU module tracking memory error was detected during initial. 
Because this is a CPU module hardware error, contact your nearest 
Mitsubishi representative.  
To replace the module, replace the standby system CPU first, then 
the control system CPU. 
 
6101 
The CPU module detected an error during the handshake for 
tracking. 
Check the condition of the other stations. 
Q4AR 
 
6200 
The standby system in a redundant system is switched to the 
control system. 
Check the control system condition. 
 
6210 
The control system in a redundant system is switched to the 
standby system. 
Check the control system condition. 
Q4AR 
 
6220 
The standby system in a redundant system could not be switched 
from the control system to the standby system because of an error 
status or other reason. 
Check the standby system condition. 
 
6221 
Switching is disabled because of a bus switching module error. 
Because this is a bus switching module hardware error, contact 
your nearest Mitsubishi representative. 
 
6222 
Switching is disabled because a multiplexed master station of a 
remote I/O network was installed in the standby station during initial. 
Check the remote I/O network setting. 
 
 
(1) In a multiple CPU system, at CPU module fault occurred at a 
station where "all station stop by stop error of PLC " was 
selected in the operating mode. 
(2) High Performance model QCPU of function version A was 
loaded in a multiple CPU system. 
(1) Read the error individual information at a peripheral device, 
check the error of the PLC resulting in CPU module fault, and 
remove the error. 
(2) Remove the High Performance model QCPU of function version 
A from the main base unit. 
 
7000 
In a multiple CPU system, station 1 resulted in stop error at power-
on and the other stations cannot start. (This error occurred at 
stations 2 to 4) 
Read the error individual information at a peripheral device, check 
the error of the CPU module resulting in CPU module fault, and 
remove the error. 
 
7002 
(1) There is no response from the target station in a multiple CPU 
system at initial communication stage. 
(2) High Performance model QCPU of function version A was 
loaded in a multiple CPU system configuration. 
(1) Reset the High Performance model QCPU and run it again. If 
the same error is displayed again, it is a hardware fault of any 
CPU module. Consult your sales representative. 
(2) Remove the High Performance model QCPU of function version 
A from the main base unit. 
 
7003 
There is no response from the target station in a multiple CPU 
system at initial communication stage. 
Reset the High Performance model QCPU and run it again. If the 
same error is displayed again, it is a hardware fault of any CPU 
module. Consult your sales representative. 
QCPU 
function 
Ver. B 
or later 
 
7010 
(1) Faulty CPU is loaded in a multiple CPU system. 
(2) High Performance model QCPU of function version A is loaded 
in a multiple CPU system configuration. 
(An error is detected at the High Performance model QCPU of 
function version B.) 
(3) In a multiple CPU system, any of stations 2 to 4 was reset during 
power-on. 
(This error occurs at only the station which was reset.) 
(1) Read the error individual information at a peripheral device, and 
change the faulty station. 
(2) Change the station of function version A for function version B. 
(3) Do not reset the CPU modules of PLC No.2 to 4. Reset the High 
Performance model QCPU of PLC No.1 and restart the multiple 
CPU system. 
 
7020 
In a multiple CPU system, a PLC fault occurred at a station where 
"all station stop by stop error of PLC" was not selected in the 
operation mode. 
(The error is detected at the High Performance model QCPU of 
other than the station where the CPU module fault occurred.) 
Read the error individual information at a peripheral device, check 
the error of the CPU module resulting in CPU module fault, and 
remove the error. 
QCPU 
function 
Ver. B 
or later 
 
9000 
Annunciator F was set ON 
Read the error individual information at a peripheral device, and 
check the program corresponding to the numerical value 
(annunciator number). 
 
9010 
Error detected by the CHK instruction. 
Read the error individual information at a peripheral device, and 
check the program corresponding to the numerical value (error 
number) there. 
 
 
9020 
Storage of data onto ROM was completed normally in automatic 
write to standard ROM. 
(BOOT LED also flickers.) 
Set the parameter enable drive to standard ROM, switch power on 
again, and perform boot operation from standard ROM. 
QCPU 
function 
Ver. B 
or later 
 
10000 
In the multiple CPU system, an error occurred in the CPU module 
other than the Process CPU/High Performance model QCPU. 
Use the software package of the corresponding CPU module to 
check the details of the error that occurred. 
QCPU 
function 
Ver. B 
or later 
 
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.