Mitsubishi Electronics Q12HCPU ユーザーズマニュアル

ページ / 212
36
(4) When a multiple CPU high speed main base unit (Q3DB) is used
(a) Available modules, the number of extension base units, and the number of 
mountable modules
*1
For the CPU modules that can be combined and their mounting positions, refer to Page 37, Section 3.1.2.
(b) Precautions
 • If I/O modules are mounted exceeding the maximum number, "SP.UNIT LAY ERR" (error code: 2124) 
occurs.
 • "Number of CPU modules" indicates the number set in "No. of PLC" of PLC parameter ("Multiple CPU 
Setting").
 • When a C Controller module which occupies three slots is used, the maximum number of mountable I/O 
modules will be two smaller than the number defined in the table on Page 36, Section 3.1.1 (4) (a).
 • A PC CPU module occupies two slots. When this module is used, the maximum number of mountable I/O 
modules will be one smaller than the number defined in the table on Page 36, Section 3.1.1 (4) (a).
Item
Description
Number of CPU 
modules
2 CPU modules
CPU No.1 (Basic model QCPU)
CPU No.2 (C Controller module or PC CPU module)
Applicable CPU 
module
*1
Basic model QCPU
Q00CPU, Q01CPU
Function version B or later
C Controller module
Q06CCPU-V, Q06CCPU-V-B, 
Q12DCCPU-V, Q24DHCCPU-V, 
Q24DHCCPU-LS
No function version restriction
PC CPU module
PPC-CPU686(MS)-64,
PPC-CPU686(MS)-128,
PPC-CPU852(MS)-512
Manual for the PC CPU 
module used
Maximum number of 
extension base units
4 extension base units
Maximum number of 
mountable I/O 
modules
25 - (Number of CPU modules)
Applicable main base 
unit
Q35DB, Q38DB, Q312DB
Applicable extension 
base unit
Type requiring no power supply 
module (Q series)
Q52B, Q55B
Type requiring power supply module 
(Q series)
Q63B, Q65B, Q68B, Q612B
Applicable extension 
cable
QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Applicable power 
supply module
Q61P-A1, Q61P-A2, Q61P, Q61P-D, Q62P, Q63P, Q64P, Q64PN