5.2.    Communication parameters for CCL003Z 
 
Title 
Function Description 
c100 
Communication error detection   
delay time 
0.0 - 100.0 sec. 
c101 
Inverter operation at the 
communication loss action 
0: Stop and controlled by cmod, fmod 
1: Operation continue 
2: Deceleration stop 
3: Coast stop 
4: Network error stop (err8 trip) 
5: Preset speed operation (by c102 setting) 
c102 
Preset speed   
operation selection 
0: None 
1 to 15: Preset speed 
c103 
Communication time-out   
condition selection 
0: Disconnection detection 
1: When communication mode enable (Both cmod and 
fmod
 are set CANopen or communication option) only 
2: 1 + Driving operation 
c120
CC-Link station number   
selection 
1 to 64 
Set the number of stations of inverters (Remote device 
station). 
c121
CC-Link baud rate selection 
0: 156kbps 
1: 625kbps 
2: 2.5Mbps 
3: 5Mbps 
4: 10Mbps 
Set the baud rate for CC-LINK network 
c122
CC-Link extended selection 
0: Occupies one station (V1.10) 
1: Occupies one station double (V2.0) 
2: Occupies one station quadruple (V2.0) 
3: Occupies one station octuple (V2.0) 
The function of remote registers can be enhanced. 
*
 
Set parameters according to the CC-Link network system.