Toshiba E6581830 ユーザーズマニュアル

ページ / 51
 
E658130 
- 17 - 
5.5. 
I/O signal list 
 
5.5.1.  One station is occupied (CC-Link Ver.1) (c122=0) 
This option occupies one station area of the buffer memory of the PLC. 
In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register 
(RWw, RWr both 4 word) in the communication data for one station area.   
 
Remote I/O
 
(Default value
 
= 0)
 
Inverter (Slave)  →  PLC (Master) 
PLC (Master)  → Inverter (Slave) 
Device No. 
Signal 
Device No. 
Signal 
RXn0 
Forward running 
RYn0 
Forward rotation command 
RXn1 Reverse 
running 
RYn1 Reverse 
rotation 
command 
RXn2 
Output terminal 1 (RY-RC) 
RYn2 
Input terminal 3 (S1) 
RXn3 
Output terminal 2 (OUT) 
RYn3 
Input terminal 4 (S2) 
RXn4 
Output terminal 3 (FL) 
RYn4 
Input terminal 5 (S3) 
RXn5 
Failure FL 
RYn5 
Input terminal 6 (S4) 
RXn6 
PI control OFF 
RYn6 
Input terminal 7 (PIOFF) 
RXn7 
Acceleration/deceleration  
pattern selection (1 or 2) 
RYn7 
Input terminal 8 (AD1) 
RXn8 
Emergency stop 
RYn8 
Input terminal 9 (ESTP) 
RXn9 
Coast stop (ST = OFF) 
RYn9 
Intercept output to inverter   
(Coast stop) 
RXnA Alarm 
RYnA Frequency 
priority 
CC-Link 
RXnB Reserved* 
RYnB Command 
priority 
CC-Link 
RXnC Monitoring 
RYnC Monitor 
command 
RXnD 
Frequency setting completion   
(RAM) 
RYnD 
Frequency setting command   
(RAM) 
RXnE Reserved* 
RYnE Reserved** 
RXnF 
Instruction code execution   
completion 
RYnF 
Instruction code execution request
RX(n+1)0  
to 
RX(n+1)9 
Reserved* 
RY(n+1)0  
to 
RY(n+1)9 
Reserved** 
RX(n+1)A Error 
status 
flag 
RY(n+1)A 
Error reset request flag   
(A reset request is during switched 
ON) 
RX(n+1)B 
Remote station ready 
RY(n+1)B 
Reserved** 
RX(n+1)C  
to 
RX(n+1)F 
Reserved* 
RY(n+1)C  
to 
RY(n+1)F 
Reserved** 
"n" is depend on the station number. 
*    The bit described "
 Reserved
 " is unstable. Don't use the “
Reserved
 " bit for the judgment. 
** Set OFF (“0”) to reserved bit. 
 
 
Remote register (Default value
 
= 0) 
RWr                                        Inverter  →  PLC 
RWw                                        PLC  → Inverter 
Address Signal Address Signal 
RWr n 
Monitor value 1 
RWw n 
Monitor code (1 and 2) 
RWr n+1 
Monitor value 2 
(output frequency) 
RWw n+1 
Set frequency 
RWr n+2 
Reply code 
RWw n+2 
Instruction code 
RWr n+3 
Read data 
RWw n+3 
Write data 
"n" is depend on the station number.