6.7. 
Program example for parameter reading 
Example 7 shows 
a ladder logic to 
read parameter f311 of station 1 inverter to D2. 
f311
: Reverse-run prohibition reading code number: 1311H (hexadecimal) 
The reply code at the time of instruction code execution is set to D1. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Check the ready of the station 1 
X0 
X0F X1 
( M0) 
SW80.0 
M0 
X20 
[ PLS  M300] 
M300 
[ SET  M301] 
M301 
X100F 
[ MOV  H1311  W102]
[ SET  Y100F] 
[ RST  M301] 
[ SET  M302] 
M302 
X100F 
[ MOV    W2    D1]
[ RST  Y100F] 
[ RST  M302] 
[ END] 
[ MOV    W3    D2]
Write  f311 read code (1311H) 
to  
Turn on the instruction code 
execution  
Read r
everse-run prohibition
 (RWr3) and   
reply code (RWr2) to D2 and D1 when   
the instruction code execution 
completion  
Turn off the instruction code 
execution  
Example 7