4.3.  Connection of CC-Link master unit and inverter 
The example of the connection of the CC-Link master unit and the inverter is shown.。 
 
 
CC-Link 
Master 
Unit 
DA 
DB 
DG 
SLD 
FG 
 
           
     
 CCL003Z 
DA 
DB 
DG 
SLD 
FG 
 
  Inverter
 
VF-S15 
R/L1 
S/L2 
T/L3 
U/T1 
V/T2 
W/T3 
 
I M 
Motor 
   
*Connection of Several Inverters 
  Factory Automation can be applied to several inverters which share a link system as   
CC-Link remote device stations and are controlled and monitored by PLC user programs. 
 
◎ 
DA,DB 
Shield twisted cable 
 DG 
  SLD / FG 
Connect the shielded wire of the dedicated CC-Link cable to the “SLD” of each   
module, and ground both ends of the shielded wire using type-D grounding (class 3   
grounding) via “FG.” 
(
The ground resistance is 100Ω or less.) 
 Terminal resistor 
Connect the terminal resistor of 110Ω.  
(130Ω is a resistance value for the CC-Link Ver.1.00 dedicated high performance cable.) 
 
 