Analog I/O Modules Calibration 
 
 
6-10 ADAM 5000 IO modules User’s Manual
 
 
4.  Issue the Analog Data Out command to the module with an 
output value of 4 mA. 
5.  Check the actual output value at the modules terminals.  If this 
does not equal 4 mA, use the "Trim" option in the "Calibrate" 
submenu to change the actual output.  Trim the module until the 
mA meter indicates exactly 4 mA, or in case of a voltage meter with 
shunt resistor, the meter indicates exactly 1 V.  (When calibrating for 
20 mA using a voltage meter and shunt resistor, the correct 
voltage should be 5 V.) 
6.  Issue the 4 mA Calibration command to indicate that the output 
is calibrated and to store the calibration parameters in the 
module's EEPROM. 
7.  Execute an Analog Data Out command with an output value 
of 20 mA.  The module's output will be approximately 20 mA. 
8.  Execute the Trim Calibration command as often as necessary until 
the output current is equal to exactly 20 mA. 
9.  Execute the 20 mA Calibration command to indicate that the 
present output is exactly 20 mA.  The analog output module 
will  store  its calibration parameters in the unit's EEPROM.