C-12        1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
1734-IE2V
2 Channel Analog Voltage Input
Configuration Data
Data Type Default
Value
Valid Data Values
Low Engineering Channel 0
INT
0
-32,768…32,767
High Engineering Channel 0
INT
10,000
-32,768…32,767
Digital Filter Channel 0
INT
0
0…10,000 ms
Low Alarm Limit Channel 0
INT
500
-32,768…32,767
High Alarm Limit Channel 0
INT
9,500
-32,768…32,767
Low Low Alarm Limit Channel 0
INT
200
-32,768…32,767
High High Alarm Limit Channel 0
INT
9,800
-32,768…32,767
Range Type Channel 0
SINT
2
0=-10…+10V
2=0…10V
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Low Engineering Channel 1
INT
0
-32,768…32,767
High Engineering Channel 1
INT
10,000
-32,768…32,767
Digital Filter Channel 1
INT
0
0…10,000 ms
Low Alarm Limit Channel 1
INT
500
-32,768…32,767
High Alarm Limit Channel 1
INT
9,500
-32,768…32,767
Low Low Alarm Limit Channel 1
INT
200
-32,768…32,767
High High Alarm Limit Channel 1
INT
9,800
-32,768…32,767
Range Type Channel 1
SINT
2
0=-10…+10V
2=0…10V
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Notch Filter (Channel 0 & 1)
SINT
2
1=50 Hz
2=60 Hz
4=250 Hz
6=500 Hz
Real-time Sample (Channel 0 & 1)
INT
100
0…10,000 ms