5-22        Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Use the controller tags in your ladder program to read input data or 
write output data.
• For RSLogix 5000 programming instructions, refer to RSLogix 
5000 Getting Results, publication 9399-RLD300GR.
• For ControlLogix controller information, refer to ControlLogix 
System User Manual, publication 1756-UM001.
• Slot Status Bits: The Slot Status bits display the connection status 
for each of the POINT I/O modules that use a rack-optimized 
connection. 
– Bit 0 is reserved for the adapter and always reports a value of 
1. 
– Each of the other bits (1 to 63) correspond to a POINT I/O 
module that you install in the POINT I/O backplane. 
– In this example, we configured the 1734-AENT adapter for 
both rack-optimized and direct connections. 
The slot status bits indicate that we installed the module in 
slot 2 with it operating correctly:
• 0=module participating with no errors and 
• 1=module not participating or connection error (typically, 
module removed/missing)