Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
132
Setting Data Links
Section 5-2
Set the following parameter in the DM Parameter Area of the PLC at the star-
tup node.
Automatic Setting, Equality Layout
Setting Range for 
Automatic Setting, 
Equality Layout
Word N
0:    Always specify 0.
– :   By other setting
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
N:    DM 30000 + 100 
×
 Controller Link Unit number
Data link mode  
001: Automatic setting, equality layout 
101: Automatic setting, 1:N allocation
(000 is for manual setting. Settings other 
than 000, 001, or 101 are invalid.)
Start word for area 1  (BCD)
Area for area 1 
Send size per node for area 1 (BCD)
Rightmost 4 digits of start word for area 2 (DM area) (BCD)
Leftmost digit of start word for 
area 2 (BCD)
First word to store link status (BCD)
BCD: Set the value as binary-coded decimal.
Nodes to participate in the data links 
The numbers indicate node numbers.
The status that is set determines whether the 
node will participate in the data links.
Participate: ON
Not participate:  OFF
15
8
7
0
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
N+1
N+2
N+3
N+4
N+5
N+6
N+7
N+8
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
N+9
Area for area 2
Send size per node for area 2 (BCD)
00
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
N+10
--- --- 62 61 60 59 58 57 56 55 54 53 52 51 50 49
N+11
Item
Setting range
Data link mode
Specify automatic (01).
Start word for area 1 
Set the word address in BCD.
CIO Area: CIO 000 to CIO 6143
LR Area: LR 00 to 199 (*)
*:  When a word between LR 000 and LR 199 is speci-
fied, the data link area will be allocated between 
CIO 1000 and CIO 1199.
Area for area 1 
Set the area for area 1 in BCD.
CIO Area: 80
LR Area: 86
Area 1 not used: 00
Send size per node for 
area 1 
Set the number of words in BCD between 0 and 1,000.
The total number of send words for area 1 and area 2 
must not exceed 1,000.
When area 1 is not used, set to 0.
Start word for area 2 
Set the word address in BCD.
DM Area: DM 0000 to DM 32767
EM Area: Banks 00 to 12, EM 0000 to EM 32767