Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
215
Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs
Section 6-6
Memory Areas
The following areas can be read. (Refer to 6-6-2 Memory Area Designations
for PLC word/bit address designations):
6-6-4
MEMORY AREA WRITE
Writes data to the specified number of consecutive words starting from the
specified word. All words must be in the same memory area. (Here, all mem-
ory areas with the same memory area code are considered as one area).
Note When data is written to the Timer/Counter PV area, the Completion Flags will
be turned OFF (0).
Command Block
Response Block
Parameters
Memory area code (command): The data area to write.
Beginning address (command): The first word/value to write. Specify 00
(Hex) for the 3rd byte.
No. of items (command): The number of items to be written. Specify 0000 to
03E5 (Hex) (0 to 997 decimal). The command can be completed normally
even if zero items are specified.
Data (command): The data to be written. PVs for timers and counters are
written as BCD. The required number of bytes in total is calculated as follows:
2 bytes 
×
 No. of items
The following data can be written. (Refer to 6-6-2 Memory Area Designations-
for the word/bit address designations):
Memory area
Data
Memory area 
code
No. of 
bytes
IR, SR, LR, HR, or 
AR
Word contents
80
2
Timer/Counter
Completion Flag status
01
1
PV
81
2
DM
Word contents
82
2
Expansion DM
Word contents
90 to 97, 98, 
and A8 to AF
2
Command 
code
01
02
Beginning address
Memory area code
Status
No. of items
00
Command 
code
01
02
Response 
code
Memory area
Data
Memory area 
code
No. of 
bytes
IR, SR, LR, HR, or 
AR
Word contents
80
2
Timer/Counter
PV
81
2
DM
Word contents
82
2
Expansion DM
Word contents
90 to 97, 98, 
and A8 to AF
2