Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
308
Status Area and Troubleshooting
Section 9-2
9-2-4
CQM1H-series Controller Link Units
Status Area
Error Information: IR 190
Data link table error 
(CIO 1500 + 25 
× 
n, bit 1) 
is 1: ON
The data link table data in 
the EEPROM of the CPU 
Unit is damaged.
Refer to 5-3 Starting and 
Stopping Data Links
 and 
reset the data link tables 
correctly. If the error occurs 
again, replace the CPU 
Unit.
There is an error in the 
data link table settings.
When using manually set 
data links, refer to 5-3 
Starting and Stopping Data 
Links 
and remake and set 
the data link tables cor-
rectly. When manually set 
data links are not being 
used, delete the data link 
tables.
Network parameter error 
(CIO 1500 + 25 
× 
n, bit 0) 
is 1: ON
The CPU Unit’s EEPROM 
data link tables or the net-
work parameters are dam-
aged.
Refer to 8-1-3 Network 
Parameters
 an
d reset the 
data correctly. If the error 
occurs again, replace the 
CPU Unit.
Either set the EEPROM 
Clear Bit in the DM Param-
eter Area to ON, or use the 
Initialize network parame-
ters operation on the Main-
tenance Menu of the 
Controller Link Support 
Software to initialize the 
network parameters and 
then cycle the power sup-
ply.
There is an error in the net-
work parameter settings, or 
node address of the local 
node is larger then the 
maximum address set 
within the network parame-
ters.
Refer to 8-1-3 Network 
Parameters
 an
d reset the 
network parameters or the 
node address.
Bit status
Probable cause
Probable remedy
1: Network parameter error (In PLC's EEPROM) 
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Error log exists