Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
316
Error Log
Section 9-3
0101 
Hex
Transmission failed; local node 
not in Network
Command block 
Bits 0 to 7:
Source node address
Bits 8 to 14: 
Source Network 
address
Bit 15: 
OFF
Response block
Bits 0 to 7: 
Destination node 
address
Bits 8 to 14: 
Destination Network 
address
Bit 15: 
ON
(1st byte: bits 8 to 15; 
2nd byte, bits 0 to 7)
Refer to page 276 
Troubleshooting 
Using Indicators 
and 
place the local node 
into Network.
No
All
0103 
Hex
Transmission failed; retry count 
exceeded
Using the Controller 
Link Support Soft-
ware or FINS 
commands, run 
echoback test and 
check operating envi-
ronment if errors 
occur.
No
All
0104 
Hex
Transmission failed; maximum 
number of frames exceeded.
Reduce the number 
of events per com-
munications cycle or 
increase the maxi-
mum number of 
network parameter 
frames.
No
All
0105 
Hex
Transmission failed; node 
address incorrect
Refer to 4-2 CJ-
series Controller Link 
Units
or 
4-4 CVM1 
and CV-series Con-
troller Link Units
 an

check node address 
settings to be sure 
they are within range 
and unique.
No
All
0106 
Hex
Transmission failed; redundant 
node address 
Correct node 
addresses so that 
they are unique 
within the same 
Network.
No
All
0107 
Hex
Transmission failed; destination 
node not in Network
Refer to 9-1 Trouble-
shooting Using Indi-
cators
 a
nd place 
destination node into 
Network.
No
All
0108 
Hex
Transmission failed; specified 
Unit does not exist
Refer to 4-4 CVM1 
and CV-series Con-
troller Link Units
 an

check unit address 
and unit number of 
destination.
No
All
Error 
code
Contents
Detail code
Correction
Written to 
EEPROM
Applicable 
PLC
1st byte
2nd byte