Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
41
Message Service Procedure
Section 2-2
6.
Set the data link mode.
Note When using fewer than 33 nodes, make sure that the Wired Network
62 Node Enable Bit in the DM Parameter Area software switches is
turned OFF to restrict the network to 32 nodes maximum. To con-
struct a network containing more than 32 nodes, all nodes must use
the CS1W-CLK21-V1 or CJ1W-CLK21-V1.
7.
Create the user program.
Contents
Method
Nodes
Page
Enable 62 nodes for a 
wired network.
Use Support Software 
for the PLC or a Pro-
gramming Console.
All nodes
This setting must be 
made when construct-
ing a network that 
uses a node address 
higher than 32 (See 
note.)
Contents
Remarks
Page
a. Prepare the send and receive 
data in memory.
Stored in the memory areas of the 
source node
b. Prepare the control data for the 
communications instruction.
c. Check the conditions for exe-
cuting the SEND/RECV or 
CMND instruction.
The standard input conditions are 
the Active Node Flags for the 
source and destination nodes, and 
the Port Enabled Flag.
d. Execute the SEND/RECV or 
CMND instruction.
---
e. Execute other instructions are 
required for the results of the 
communications instruction, 
(e.g., retry or error processing 
if an error occurs).
The standard input condition is the 
Port Error Flags.
C200HX/HG/HE PLCs have 1 
communications port for each 
operating level. When 2 or more 
communications instructions are 
executed at the same time, exclu-
sive control is necessary.
CS-series, CJ-series, CVM1, and 
CV-series PLCs have 8 communi-
cations ports. When 9 or more 
communications instructions are 
executed at the same time, exclu-
sive control is necessary.
CQM1H-series PLCs have only 1 
communications port. When 2 or 
more communications instructions 
are executed at the same time, 
exclusive control is necessary.